6381Y Cable to BS6004
- Eland Product Group:
- A1F
- Application:
- Suitable for DC power supplies on Telecom equipment and power applications where flexibility is required.
- Standards:
- Generally to BS6004
- Conductor:
- Class 5 flexible plain copper conductors to BS EN 60228:2005 (previously BS6360)
- Insulation:
- PVC (Polyvinyl Chloride) Type TI1 to BS7655
- Sheath:
PVC (Polyvinyl Chloride) Type TM1 to BS7655 with oxygen index > 30%
Flame retardant to BS4066 Part 1
Meets requirements for flammability as required by BT specification M231- Sheath Colour (Insulation Colour):
- Blue (Blue), Grey (Grey), Green/Yellow (Green/Yellow), Brown (Brown), Special colours to order
- Voltage Rating:
10-35mm²: 450/750V
50mm²+: 600/1000V- Temperature Rating:
- 70°C
- Minimum Bending Radius:
Up to 50mm²:
3 x overall diameter
Above 70mm²:
4 x overall diameter
RoHS Compliant
| No. of Cores x Nominal Cross Sectional Area # x mm² | Nominal Thickness of Insulation mm | Nominal Thickness of Sheath mm | Nominal Overall Diameter mm | Nominal Weightkg/Km |
|---|---|---|---|---|
| 1 x 1.5 | 0.9 | 0.8 | 4.91 | 38.0 |
| 1 x 2.5 | 0.9 | 0.8 | 5.35 | 48.8 |
| 1 x 4.0 | 1.0 | 0.9 | 6.25 | 70.7 |
| 1 x 6.0 | 1.1 | 0.9 | 7.60 | 100.5 |
| 1 x 10.0 | 1.2 | 1.1 | 8.56 | 151.6 |
| 1 x 16.0 | 1.2 | 1.1 | 9.75 | 212.7 |
| 1 x 25.0 | 1.4 | 1.1 | 11.50 | 307.0 |
| 1 x 35.0 | 1.4 | 1.1 | 12.50 | 404.5 |
| 1 x 50.0 | 1.4 | 1.4 | 15.10 | 579.2 |
| 1 x 70.0 | 1.4 | 1.4 | 16.95 | 768.2 |
| 1 x 95.0 | 1.6 | 1.5 | 19.10 | 1007.3 |
| 1 x 120.0 | 1.6 | 1.8 | 21.60 | 1281.3 |
| 1 x 150.0 | 1.8 | 1.8 | 23.40 | 1570.6 |
| 1 x 185.0 | 2.0 | 1.8 | 25.50 | 1895.0 |
| 1 x 240.0 | 2.2 | 1.8 | 28.50 | 2435.0 |
| 1 x 300.0 | 2.4 | 2.0 | 31.20 | 3050.0 |
| 1 x 400.0 | 2.6 | 2.1 | 35.30 | 4035.0 |
| 1 x 500.0 | 2.8 | 2.2 | 38.80 | 4970.0 |
| 1 x 630.0 | 2.8 | 2.4 | 43.80 | 6510.0 |

