Coil End Lead Cable to BS6195
- Eland Product Group:
- A6K
- Application:
- Coil leads are used mainly in electrical machinery and panel wiring. The HOFR sheath resists oil and varnish and the stranding is designed as a compromise between flexibility and positional stability. Also suitable as an alternative to tri-rated and bi-rated cable in certain applications.
- Standards:
- BS6195 Type 4
- Conductor:
- Class 5 flexible tinned copper to BS EN 60228:2005 (previously BS6360)
- Separator:
- PETP (Polyethelene Terephthalate) tape
- Insulation:
4A, 4C: EPR-HOFR (Ethylene Propylene Rubber - Heat and Oil Resistant and Flame Retardant) Type FR1 to BS7655
4D, 4E, 4F: EPR-HOFR (Ethylene Propylene Rubber - Heat and Oil Resistant and Flame Retardant) Type FR2 to BS7655- Sheath:
- CPE (Chlorinated Polyethylene) rubber compound
- Sheath Colour:
- Black
- Voltage Rating:
Type 4A: 300/500V
Type 4C: 600/1000V
Type 4D: 1900/3300V
Type 4E: 3800/6600V
Type 4F: 6350/11000V- Temperature Rating:
- -30°C to +90°C
- Minimum bending radius:
Up to 25mm²:
6 x overall diameter
Above 25mm²:
8 x overall diameter
RoHS Compliant
| Cable Type | No. of Cores x Nominal Cross Sectional Area# x mm² | Nominal Thickness of Insulationmm | Overall Diameter Max.mm | Nominal Weightkg/Km |
|---|---|---|---|---|
| 4A | 1 x 0.75 | 0.8 | 3.5 | 14.5 |
| 4A | 1 x 1.00 | 0.8 | 3.7 | 22.5 |
| 4A | 1 x 1.50 | 0.8 | 4.0 | 28.4 |
| 4A | 1 x 2.50 | 0.9 | 4.6 | 41.5 |
| 4A | 1 x 4.00 | 1.0 | 5.4 | 61.0 |
| 4A | 1 x 6.00 | 1.0 | 6.5 | 88.0 |
| 4A | 1 x 10.00 | 1.2 | 7.9 | 141.0 |
| 4C | 1 x 10.00 | 1.5 | 8.5 | 130.0 |
| 4C | 1 x 16.00 | 1.5 | 9.6 | 190.0 |
| 4C | 1 x 25.00 | 1.6 | 11.4 | 290.0 |
| 4C | 1 x 35.00 | 1.6 | 12.8 | 380.0 |
| 4C | 1 x 50.00 | 1.7 | 14.8 | 510.0 |
| 4C | 1 x 70.00 | 1.8 | 17.2 | 750.0 |
| 4C | 1 x 95.00 | 2.0 | 19.7 | 935.0 |
| 4C | 1 x 120.00 | 2.2 | 21.9 | 1160.0 |
| 4C | 1 x 150.00 | 2.3 | 24.1 | 1450.0 |
| 4C | 1 x 185.00 | 2.4 | 26.3 | 1770.0 |
| 4C | 1 x 240.00 | 2.4 | 28.3 | 2260.0 |
| 4C | 1 x 300.00 | 2.6 | 33.0 | 2760.0 |
| 4C | 1 x 400.00 | 2.8 | 37.4 | 3880.0 |
| 4C | 1 x 500.00 | 3.2 | 38.0 | 4650.0 |
| 4C | 1 x 630.00 | 3.3 | 43.0 | 6220.0 |
| 4D | 1 x 2.50 | 2.8 | 8.5 | 100.0 |
| 4D | 1 x 4.00 | 2.8 | 9.1 | 115.0 |
| 4D | 1 x 6.00 | 2.8 | 10.3 | 141.0 |
| 4D | 1 x 10.00 | 2.8 | 11.3 | 216.0 |
| 4D | 1 x 16.00 | 2.8 | 12.4 | 288.0 |
| 4D | 1 x 25.00 | 2.8 | 13.8 | 392.0 |
| 4D | 1 x 35.00 | 2.8 | 15.2 | 509.0 |
| 4D | 1 x 50.00 | 2.8 | 17.1 | 682.0 |
| 4D | 1 x 70.00 | 2.8 | 19.2 | 894.0 |
| 4D | 1 x 95.00 | 3.0 | 22.0 | 1168.0 |
| 4D | 1 x 120.00 | 3.0 | 23.5 | 1433.0 |
| 4D | 1 x 150.00 | 3.0 | 25.5 | 1734.0 |
| 4D | 1 x 185.00 | 3.0 | 27.5 | 2073.0 |
| 4D | 1 x 240.00 | 3.0 | 30.6 | 2657.0 |
| 4D | 1 x 300.00 | 3.0 | 33.8 | 3279.0 |
| 4D | 1 x 400.00 | 3.0 | 37.8 | 4229.0 |
| 4E | 1 x 16.00 | 5.0 | 17.2 | 408.0 |
| 4E | 1 x 25.00 | 5.0 | 18.6 | 527.0 |
| 4E | 1 x 35.00 | 5.0 | 20.0 | 656.0 |
| 4E | 1 x 50.00 | 5.0 | 22.1 | 832.0 |
| 4E | 1 x 70.00 | 5.0 | 24.2 | 1053.0 |
| 4E | 1 x 95.00 | 5.0 | 26.3 | 1304.0 |
| 4E | 1 x 120.00 | 5.0 | 27.8 | 1634.0 |
| 4E | 1 x 150.00 | 5.0 | 29.8 | 1894.0 |
| 4E | 1 x 185.00 | 5.0 | 32.1 | 2242.0 |
| 4E | 1 x 240.00 | 5.0 | 35.1 | 2842.0 |
| 4F | 1 x 25.00 | 7.6 | 24.1 | 764.0 |
| 4F | 1 x 35.00 | 7.6 | 25.5 | 911.0 |
| 4F | 1 x 50.00 | 7.6 | 27.3 | 1114.0 |
| 4F | 1 x 70.00 | 7.6 | 29.4 | 1344.0 |
| 4F | 1 x 95.00 | 7.6 | 31.5 | 1610.0 |
| 4F | 1 x 120.00 | 7.6 | 33.3 | 1919.0 |
| 4F | 1 x 150.00 | 7.6 | 35.3 | 2248.0 |
| 4F | 1 x 185.00 | 7.6 | 37.3 | 2616.0 |
| 4F | 1 x 240.00 | 7.6 | 40.3 | 3252.0 |

