BS7835 Cables

11kV XLPE LSZH Cable BS7835

Restriction of the use of Hazardous SubstancesBritish Standards InstituteInternational Electrotechnical Commission

Eland Product Group: A9M

Application: Power cables for power networks, underground, outdoors and in cable ducting. In particular for installation where fire, smoke emission and toxic fumes create a potential threat.

Standards: BS7835, IEC 60754-1

Conductor: Class 2 stranded plain copper conductor to BS EN 60228:2005 (previously BS6360)

Conductor screen: Semi-conducting material

Insulation: XLPE (Cross-Linked Polyethylene) Type GP8 to BS7655

Insulation Screen: Semi-conducting material

Metallic Screen: Individual and overall copper tape screen to BS6622

Filler: PETP (Polyethylene Terephthalate) fibres

Separator: Binding tape

Bedding: LSZH (Low Smoke Zero Halogen)

Armouring:
Single Core: Aluminium Wire Armoured (AWA)
MultiCore: Steel Wire Armoured (SWA)

Sheath: LSZH (Low Smoke Zero Halogen)

Colour: Red or Black

Voltage Rating: 6350/11000V

Temperature Rating: 0°C to +90°C

Combustion Characteristics:
Oxygen index: 35

Temperature index: 280°C

HCL emission: 0.5% in accordance with BS EN 50267-2-1

Low smoke classification based on 3 metre cube test

Completed cables comply with the requirements of fire test BS4066-3 Category 3

Minimum Bending Radius:
Single Core: 15 x overall diameter
Three Core: 12 x overall diameter
(Single Core 12 x overall diameter and 3 core 10 x overall diameter where bands are positioned adjacent to joint or terminations provided that the bending is carefully controlled by the use of a former)

For more information please consult a member of the Sales Team.

11kV XLPE LSZH Cable BS7835

Eland Part Number
No. of Cores x Nominal Cross Sectional Area
# x mm²
Nominal Overall Diameter
mm
A9M11KV01050L* 1 x 50 28.50
A9M11KV01070L* 1 x 70 30.00
A9M11KV01095L* 1 x 95 31.70
A9M11KV01120L* 1 x 120 33.90
A9M11KV01150L* 1 x 150 35.70
A9M11KV01185L* 1 x 185 37.50
A9M11KV01240L* 1 x 240 40.00
A9M11KV01300L* 1 x 300 43.00
A9M11KV01400L* 1 x 400 45.80
A9M11KV01500L* 1 x 500 50.50
A9M11KV01630L* 1 x 630 54.80
A9M11KV01800L* 1 x 800 59.20
A9M11KV011000L* 1 x 1000 64.30
A9M11KV03025L* 3 x 25 48.80
A9M11KV03035L* 3 x 35 51.60
A9M11KV03050L* 3 x 50 54.60
A9M11KV03070L* 3 x 70 58.50
A9M11KV03095L* 3 x 95 62.60
A9M11KV03120L* 3 x 120 66.60
A9M11KV03150L* 3 x 150 69.80
A9M11KV03185L* 3 x 185 74.10
A9M11KV03240L* 3 x 240 81.20
A9M11KV03300L* 3 x 300 87.00