33kV XLPE Cable
- Eland Product Group:
- A9M
- Application:
- Power cables for power networks, underground, outdoors and in cable ducting.
- Standards:
- BS6622
- Conductor:
- Class 2 stranded plain copper conductor to BS EN 60228:2005 (previously BS6360)
- Conductor screen:
- Semi-conducting material
- Insulation:
- XLPE (Cross-Linked Polyethylene) Type GP8 to BS7655
- Insulation Screen:
- Semi-conducting material
- Metallic Screen:
- Individual and overall copper tape screen to BS6622
- Filler:
- PETP (Polyethylene Terephthalate) fibres
- Separator:
- Binding tape
- Bedding:
- PVC (Polyvinyl Chloride) Type TM1 to BS7655
- Armouring:
Single Core: Aluminium Wire Armoured (AWA)
Multi-core: Steel Wire Armoured (SWA)- Sheath:
- PVC (Polyvinyl Chloride) Type TM1 to BS7655
- Colour:
- Red or Black
- Voltage Rating:
- 19000/33000V
- Temperature Rating:
- 0°C to +90°C
- Minimum Bending Radius:
Single Core: 15 x overall diameter
Three Core: 12 x overall diameter
(Single Core 12 x overall diameter and 3 core 10 x overall diameter where bands are positioned adjacent to joint or terminations provided that the bending is carefully controlled by the use of a former)
| Cable Type | Nominal Cross Sectional Areamm2 | Nominal Diameter Under Armourmm | Nominal Diameter Over Armourmm | Nominal Diameter Overallmm | Nominal Weightkg/Km | Continuous Current Rating in Ground - TrefoilAmps | Continuous Current Rating in Ground - FlatAmps |
|---|---|---|---|---|---|---|---|
| Copper | 1 x 70 | 32.6 | 36.6 | 41.0 | 2300 | 270 | 280 |
| Copper | 1 x 95 | 34.3 | 38.3 | 42.9 | 2650 | 320 | 335 |
| Copper | 1 x 120 | 35.9 | 39.9 | 44.5 | 3000 | 360 | 380 |
| Copper | 1 x 150 | 37.5 | 42.5 | 47.3 | 3500 | 410 | 430 |
| Copper | 1 x 185 | 39.3 | 44.3 | 49.3 | 4000 | 455 | 485 |
| Copper | 1 x 240 | 41.7 | 46.7 | 51.7 | 4650 | 520 | 560 |
| Copper | 1 x 300 | 44.2 | 49.2 | 54.4 | 5450 | 580 | 640 |
| Copper | 1 x 400 | 47.3 | 52.3 | 57.7 | 6350 | 650 | 730 |
| Copper | 1 x 500 | 50.5 | 55.5 | 61.1 | 7600 | 710 | 830 |
| Copper | 1 x 630 | 54.2 | 59.2 | 65.0 | 9150 | 760 | 940 |
| Copper | 1 x 800 | 60.5 | 65.5 | 71.6 | 11100 | 810 | 1060 |
| Copper | 1 x 1000 | 65.0 | 70.0 | 76.5 | 13400 | 860 | 1170 |
| Copper | 3 x 50 | 65.1 | 71.4 | 78.2 | 9150 | 210 | 210 |
| Copper | 3 x 70 | 68.8 | 75.1 | 82.1 | 10300 | 250 | 250 |
| Copper | 3 x 95 | 72.6 | 78.9 | 86.1 | 11600 | 300 | 300 |
| Copper | 3 x 120 | 76.3 | 82.6 | 90.0 | 12800 | 340 | 340 |
| Copper | 3 x 150 | 79.3 | 85.6 | 93.2 | 14050 | 380 | 380 |
| Copper | 3 x 185 | 83.4 | 89.7 | 97.5 | 15650 | 430 | 430 |
| Copper | 3 x 240 | 88.8 | 95.1 | 103.3 | 18200 | 500 | 500 |
| Copper | 3 x 300 | 93.9 | 100.2 | 108.8 | 21100 | 540 | 540 |
| Copper | 3 x 400 | 100.8 | 107.1 | 116.1 | 24200 | 600 | 600 |
| Aluminium | 1 x 70 | 32.6 | 36.6 | 41.0 | 1850 | 210 | 215 |
| Aluminium | 1 x 95 | 34.3 | 38.3 | 42.9 | 2100 | 250 | 260 |
| Aluminium | 1 x 120 | 35.9 | 39.9 | 44.5 | 2250 | 280 | 295 |
| Aluminium | 1 x 150 | 37.5 | 42.5 | 47.3 | 2600 | 320 | 330 |
| Aluminium | 1 x 185 | 39.3 | 44.3 | 49.3 | 2850 | 360 | 375 |
| Aluminium | 1 x 240 | 41.7 | 46.7 | 51.7 | 3150 | 415 | 440 |
| Aluminium | 1 x 300 | 44.2 | 49.2 | 54.4 | 3600 | 475 | 495 |
| Aluminium | 1 x 400 | 47.3 | 52.3 | 57.7 | 4000 | 540 | 570 |
| Aluminium | 1 x 500 | 50.5 | 55.5 | 61.1 | 4500 | 610 | 650 |
| Aluminium | 1 x 630 | 54.2 | 59.2 | 65.0 | 5250 | 680 | 750 |
| Aluminium | 1 x 800 | 60.5 | 65.5 | 71.6 | 6150 | 770 | 860 |
| Aluminium | 1 x 1000 | 65.0 | 70.0 | 76.5 | 7200 | 859 | 960 |
| Aluminium | 3 x 50 | 65.1 | 71.4 | 78.2 | 8300 | 160 | 160 |
| Aluminium | 3 x 70 | 68.8 | 75.1 | 82.1 | 9050 | 195 | 195 |
| Aluminium | 3 x 95 | 72.6 | 78.9 | 86.1 | 9800 | 230 | 230 |
| Aluminium | 3 x 120 | 76.3 | 82.6 | 90.0 | 10600 | 265 | 265 |
| Aluminium | 3 x 150 | 79.3 | 85.6 | 93.2 | 11350 | 300 | 300 |
| Aluminium | 3 x 185 | 83.4 | 89.7 | 97.5 | 12250 | 335 | 335 |
| Aluminium | 3 x 240 | 88.8 | 95.1 | 103.3 | 13700 | 380 | 380 |
| Aluminium | 3 x 300 | 93.9 | 100.2 | 108.8 | 15500 | 435 | 435 |
| Aluminium | 3 x 400 | 100.8 | 107.1 | 116.1 | 16750 | 490 | 490 |