YY LSZH Control Flexible Cable
- Eland Product Group:
- A5L
- Application:
- For installation where fire, smoke emission and toxic fumes create a potential threat to life and equipment. Used as interconnecting cable for measuring, controlling or regulation in control equipment for assembly and production lines, conveyors and for computer units. Suitable for fixed installations or for flexible use in conditions of light mechanical stress. Can be used outdoors when protected, and in dry or moist conditions indoors.
- Standards:
- Generally to BS6500, VDE0250,
IEC 60332-3, IEC 60092-353,
IEC 60754-1 - Conductor:
- Class 5 flexible plain stranded copper conductors to
DIN VDE 0295:1995-06 or IEC 60228 - Insulation:
- XLPE (Cross-Linked Polyethylene)
- Sheath:
- LSZH (Low Smoke Zero Halogen)
- Sheath Colour:
- Grey
- Voltage Rating:
- 300/500V
- Temperature Rating:
Fixed: -35°C to +85°C
Flexing: -5°C to +85°C- Minimum Bending Radius:
- 10 x overall diameter
- Core Identification:
- Black with White numbers. (3 cores and above to include Green/Yellow). Coloured cores available.
Specifications Data
Download detailed YY LSZH Control Flexible Cable specifications as a PDF file (223kb)
| No. of Cores x Nominal Cross Sectional Area# x mm² | Nominal Overall Diametermm | Nominal Weightkg/ Km | FCGA2/A2P Gland |
|---|---|---|---|
| 2 x 0.75 | 5.1 | 39 | -/20S |
| 2 x 1.00 | 5.3 | 49 | -/20S |
| 2 x 1.50 | 6.2 | 61 | -/20S |
| 2 x 2.50 | 7.3 | 92 | -/20 |
| 3 x 0.75 | 5.4 | 50 | -/20S |
| 3 x 1.00 | 5.6 | 60 | -/20S |
| 3 x 1.50 | 6.5 | 79 | -/20S |
| 3 x 2.50 | 7.7 | 119 | -/20 |
| 3 x 4.00 | 9.3 | 176 | 20S/20 |
| 3 x 6.00 | 11.0 | 255 | 20S/20 |
| 4 x 0.50 | 5.4 | 46 | -/20S |
| 4 x 0.75 | 5.9 | 59 | -/20S |
| 4 x 1.00 | 6.5 | 69 | -/20S |
| 4 x 1.50 | 7.4 | 92 | -/20 |
| 4 x 2.50 | 8.5 | 148 | 20S/20 |
| 4 x 4.00 | 10.2 | 219 | 20S/20 |
| 4 x 6.00 | 12.3 | 323 | 20/25 |
| 4 x 10.00 | 15.0 | 513 | 25/25 |
| 4 x 16.00 | 19.2 | 844 | 25/32 |
| 4 x 25.00 | 23.0 | 1252 | 32/32 |
| 4 x 35.00 | 26.7 | 1658 | 40/40 |
| 4 x 50.00 | 31.5 | 2360 | 40/40 |
| 4 x 95.00 | 41.1 | 4259 | 50/63 |
| 4 x 150.00 | 45.1 | 5263 | 63S/- |
| 5 x 0.50 | 6.2 | 57 | -/20S |
| 5 x 0.75 | 6.7 | 68 | -/20S |
| 5 x 1.00 | 6.9 | 83 | -/20S |
| 5 x 1.50 | 7.9 | 109 | -/20 |
| 5 x 2.50 | 9.7 | 180 | 20S/20 |
| 5 x 4.00 | 11.6 | 269 | 20/20 |
| 5 x 6.00 | 13.5 | 391 | 25/25 |
| 5 x 10.00 | 17.1 | 650 | 25/25 |
| 5 x 16.00 | 21.3 | 1012 | 32/32 |
| 5 x 25.00 | 25.8 | 1548 | 32/32 |
| 5 x 35.00 | 29.5 | 2029 | 40/40 |
| 5 x 50.00 | 34.7 | 2920 | 50S/50 |
| 5 x 95.00 | 45.6 | 5292 | 50/63 |
| 6 x 1.00 | 7.0 | 101 | -/20 |
| 7 x 0.50 | 6.6 | 70 | -/20S |
| 7 x 0.75 | 7.1 | 90 | -/20 |
| 7 x 1.00 | 7.5 | 104 | -/20 |
| 7 x 1.50 | 9.0 | 147 | 20S/20 |
| 7 x 2.50 | 10.1 | 232 | 20S/20 |
| 10 x 0.50 | 8.4 | 97 | 20S/20 |
| 12 x 0.75 | 9.4 | 146 | 20S/20 |
| 12 x 1.00 | 9.9 | 174 | 20S/20 |
| 12 x 1.50 | 11.6 | 237 | 20/20 |
| 12 x 2.50 | 13.9 | 377 | 25/25 |
| 18 x 0.75 | 11.1 | 211 | 20S/20 |
| 18 x 1.00 | 11.7 | 252 | 20S/20 |
| 18 x 1.50 | 13.7 | 347 | 25/25 |
| 21 x 1.50 | 14.9 | 403 | 25/25 |
| 25 x 0.75 | 13.5 | 289 | 25/25 |
| 25 x 1.00 | 14.3 | 346 | 25/25 |
| 25 x 1.50 | 16.9 | 490 | 25/25 |