Section 12 Fire Integrity Cable - London Underground
- Eland Product Group:
- A5K
- Application:
- For installation typically in public help points (PHP), public address (PA), station announcement platforms (SAP) & CCTV camera power systems. This Low Smoke Zero Halogen cable has been designed to provide superior flame retardance and circuit integrity, together with optimised ease of installation characteristics and complies with LU Section 12 station regulations.
- Standards:
BS7629-1, BS 5839-1:2002, BS 5839-1:2002, BS 8434-1:2003, BS EN 50200 PH30, BS 6387 C W Z, IEC 60332-3, IEC 60332-1, BS EN 50265, BS EN 50266, IEC 60754, BS EN 50267, IEC 61034, BS EN 50268.- Conductor:
- Class 1 solid or Class 2 stranded annealed plain copper conductors to BS EN 60228:2005 (previously BS6360)
- Insulation:
- Silicone rubber
- Separator:
- Unspecified material
- Screen:
- Aluminium/polyester laminated tape
- Drain Wire:
- Tinned copper
- Sheath:
- High performance thermoplastic LSZH (Low Smoke Zero Halogen)
- Sheath Colour:
- White
- Voltage:
- 300/500 V
- Temperature Rating:
- -40°C to +90°C
This cable should not be used when either the ambient
or cable temperature is below 0°C - Minimum Bending Radius:
- 6 x overall diameter
- Core Identification:
2 Cores: Brown, Blue
3 Cores: Brown, Black, Grey
4 Cores: Blue, Brown, Black, Grey
7 Cores: Blue, Brown, Black, Grey
Specifications Data
Download detailed Section 12 Fire Integrity Cable - London Underground specifications as a PDF file (191kb)
| No. of Cores x Nominal Cross Sectional Area# x mm² | Nominal Overall Diametermm | Nominal Weightkg/Km |
|---|---|---|
| 2 x 1.00 | 7.0 | 83 |
| 2 x 1.50 | 7.9 | 110 |
| 2 x 2.50 | 9.3 | 160 |
| 3 x 1.00 | 7.3 | 95 |
| 3 x 1.50 | 8.3 | 128 |
| 3 x 2.50 | 9.9 | 190 |
| 4 x 1.00 | 8.2 | 115 |
| 4 x 1.50 | 9.5 | 160 |
| 4 x 2.50 | 11.3 | 235 |
| 7 x 1.00 | 10.5 | 175 |
| 7 x 1.50 | 12.2 | 250 |