FireForce Fire Performance Cable PH30
- Eland Product Group:
- A5K
- Application:
- For fixed installation typically in fire alarm and emergency lighting circuits where circuit integrity must be maintained. For installation where fire, smoke emission and toxic fumes create a potential threat to life and equipment.
- Standards:
BS 7629-1
BS 6387 C W Z
BS 5839-1 clause 26.2
BS EN 50200 PH30
BS 8434-1- Conductor:
- Class 1 solid copper conductors
- Insulation:
- Special compound silicone and rubber mix
- Screen:
- CAM (Collective Aluminium Mylar)
- Sheath:
- LSZH (Low Smoke Zero Halogen)
- Sheath Colour:
- Red or White
- Core Identification:
2 Cores: Brown, Blue
4 Cores: Blue, Brown, Black, Grey- Voltage :
- 300/500V
- Temperature Rating:
- -30°C to +70°C
- Minimum Bending Radius:
- 6 x overall diameter
Specifications Data
Download detailed FireForce Fire Performance Cable PH30 specifications as a PDF file (280kb)
| No. of Cores x Nominal Cross Sectional Area# x mm² | Nominal Thickness of Insulationmm | Nominal Thickness of Sheathmm | Nominal Overall Diametermm | Nominal Weightkg/Km |
|---|---|---|---|---|
| 2 x 1.00 | 0.7 | 1.2 | 7.08 | 75.72 |
| 2 x 1.50 | 0.7 | 1.4 | 8.07 | 101.39 |
| 2 x 2.50 | 0.8 | 1.4 | 9.09 | 141.86 |
| 2 x 4.00 | 0.9 | 1.5 | 12.00 | 226.91 |
| 4 x 1.00 | 0.7 | 1.4 | 9.02 | 121.00 |
| 4 x 1.50 | 0.7 | 1.4 | 9.08 | 150.51 |
| 4 x 2.50 | 0.8 | 1.5 | 11.05 | 222.00 |
| 4 x 4.00 | 0.9 | 1.7 | 14.02 | 366.00 |