Steel Wire Armoured (SWA) BS6724 Cable LSZH
- Eland Product Group:
- A9S
- Application:
- Power and auxiliary control cables for power networks, underground, outdoors, indoors and in cable ducting. For installation where fire, smoke emission and toxic fumes create a potential threat to life and equipment.
- Standards:
- BS6724
- Conductor:
- Class 2 stranded plain annealed copper conductor to BS EN 60228:2005 (previously BS6360)
- Insulation:
- XLPE (Cross-Linked Polyethylene)
- Bedding:
- LSZH (Low Smoke Zero Halogen)
- Armouring:
Single Core: AWA (Aluminium Wire Armour)
Multi Core: SWA (Steel Wire Armour)- Sheath:
- LSZH (Low Smoke Zero Halogen)
- Sheath Colour:
- Black
- Voltage Rating:
- 600/1000V
- Temperature Rating:
- 0°C to +90°C
- Minimum Bending Radius:
1.5mm² - 16mm²:
6 x overall diameter
25mm² and above:
8 x overall diameter- Core Identification:
1 Core: Brown
2 Cores: Brown, Blue
3 Cores: Brown, Black, Grey
4 Cores: Blue, Brown, Black, Grey
5 Cores: Green/Yellow, Blue, Brown, Black, Grey
Alternative core identification: White Cores with Black numbers
Specifications Data
Download detailed Steel Wire Armoured (SWA) BS6724 Cable LSZH specifications as a PDF file (296kb)
| No. of Cores x Cross Sectional Area# x mm² | Nominal Thickness of Insulationmm | Nominal Diameter Under Armourmm | Nominal Overall Diametermm | Nominal Weightkg/Km |
|---|---|---|---|---|
| 1 x 50 | 1.0 | 12.7 | 17.5 | 800 |
| 1 x 70 | 1.1 | 14.7 | 20.2 | 960 |
| 1 x 95 | 1.1 | 16.6 | 22.3 | 1240 |
| 1 x 120 | 1.2 | 18.5 | 24.2 | 1510 |
| 1 x 150 | 1.4 | 20.8 | 27.4 | 1900 |
| 1 x 185 | 1.6 | 23.2 | 30.0 | 2320 |
| 1 x 240 | 1.7 | 26.0 | 32.8 | 2930 |
| 1 x 300 | 1.8 | 28.6 | 35.6 | 3580 |
| 1 x 400 | 2.0 | 32.4 | 40.4 | 4600 |
| 1 x 500 | 2.2 | 36.0 | 44.2 | 5770 |
| 1 x 630 | 2.4 | 40.0 | 48.8 | 7250 |
| 1 x 800 | 2.6 | 45.6 | 55.4 | 9381 |
| 1 x 1000 | 2.8 | 50.6 | 60.6 | 11540 |
| 2 x 1.5 | 0.6 | 7.3 | 12.1 | 302 |
| 2 x 2.5 | 0.7 | 8.5 | 13.6 | 346 |
| 2 x 4.0 | 0.7 | 9.4 | 14.7 | 410 |
| 2 x 6.0 | 0.7 | 10.5 | 15.9 | 499 |
| 2 x 10.0 | 0.7 | 12.3 | 18.0 | 648 |
| 2 x 16.0 | 0.7 | 14.3 | 20.4 | 978 |
| 2 x 25.0 | 0.9 | 14.7 | 20.4 | 1290 |
| 2 x 35.0 | 0.9 | 16.8 | 23.3 | 1500 |
| 2 x 50.0 | 1.0 | 19.0 | 25.8 | 1890 |
| 2 x 70.0 | 1.1 | 22.0 | 29.0 | 2450 |
| 2 x 95.0 | 1.1 | 25.1 | 33.1 | 3300 |
| 2 x 120.0 | 1.2 | 27.9 | 36.1 | 4020 |
| 2 x 150.0 | 1.4 | 30.9 | 39.3 | 4750 |
| 2 x 185.0 | 1.6 | 34.9 | 44.7 | 6180 |
| 2 x 240.0 | 1.7 | 39.0 | 49.0 | 7570 |
| 3 x 1.5 | 0.6 | 7.8 | 12.6 | 330 |
| 3 x 2.5 | 0.7 | 9.2 | 14.1 | 390 |
| 3 x 4.0 | 0.7 | 10.0 | 15.3 | 464 |
| 3 x 6.0 | 0.7 | 11.2 | 16.6 | 568 |
| 3 x 10.0 | 0.7 | 13.1 | 19.5 | 866 |
| 3 x 16.0 | 0.7 | 15.3 | 21.6 | 1152 |
| 3 x 25.0 | 0.9 | 18.9 | 25.5 | 1800 |
| 3 x 35.0 | 0.9 | 21.3 | 28.0 | 2230 |
| 3 x 50.0 | 1.0 | 21.7 | 28.5 | 2490 |
| 3 x 70.0 | 1.1 | 25.2 | 32.2 | 3290 |
| 3 x 95.0 | 1.1 | 28.8 | 37.0 | 4440 |
| 3 x 120.0 | 1.2 | 32.0 | 40.4 | 5470 |
| 3 x 150.0 | 1.4 | 35.9 | 45.5 | 6930 |
| 3 x 185.0 | 1.6 | 40.0 | 49.8 | 8350 |
| 3 x 240.0 | 1.7 | 44.9 | 55.1 | 10400 |
| 3 x 300.0 | 1.8 | 49.8 | 60.2 | 12600 |
| 3 x 400.0 | 2.0 | 55.8 | 66.6 | 14600 |
| 4 x 1.5 | 0.6 | 8.5 | 13.5 | 365 |
| 4 x 2.5 | 0.7 | 9.9 | 15.0 | 438 |
| 4 x 4.0 | 0.7 | 11.0 | 16.4 | 532 |
| 4 x 6.0 | 0.7 | 12.3 | 18.7 | 764 |
| 4 x 10.0 | 0.7 | 14.5 | 21.1 | 1013 |
| 4 x 16.0 | 0.7 | 17.0 | 22.9 | 1360 |
| 4 x 25.0 | 0.9 | 21.0 | 27.6 | 2160 |
| 4 x 35.0 | 0.9 | 23.6 | 30.4 | 2690 |
| 4 x 50.0 | 1.0 | 25.0 | 32.0 | 3130 |
| 4 x 70.0 | 1.1 | 29.5 | 37.7 | 4500 |
| 4 x 95.0 | 1.1 | 33.3 | 41.7 | 5600 |
| 4 x 120.0 | 1.2 | 37.5 | 47.1 | 7400 |
| 4 x 150.0 | 1.4 | 41.6 | 51.4 | 8780 |
| 4 x 185.0 | 1.6 | 46.4 | 56.6 | 10630 |
| 4 x 240.0 | 1.7 | 52.6 | 63.0 | 13390 |
| 4 x 300.0 | 1.8 | 58.0 | 68.8 | 16290 |
| 4 x 400.0 | 2.0 | 65.4 | 78.1 | 19800 |
| 5 x 1.5 | 0.6 | 9.7 | 14.3 | 410 |
| 5 x 2.5 | 0.7 | 11.7 | 16.3 | 470 |
| 5 x 4.0 | 0.7 | 13.0 | 17.8 | 710 |
| 5 x 6.0 | 0.7 | 14.5 | 20.0 | 876 |
| 5 x 10.0 | 0.7 | 17.2 | 22.9 | 1165 |
| 5 x 16.0 | 0.7 | 20.0 | 26.6 | 1742 |
| 5 x 25.0 | 0.9 | 24.7 | 31.5 | 2323 |
| 5 x 35.0 | 0.9 | 27.8 | 34.8 | 2932 |
| 5 x 50.0 | 1.0 | 32.4 | 40.4 | 4192 |
| 5 x 70.0 | 1.1 | 37.9 | 46.3 | 5336 |
| 7 x 1.5 | 0.6 | 10.2 | 15.2 | 470 |
| 7 x 2.5 | 0.7 | 12.3 | 17.1 | 600 |
| 7 x 4.0 | 0.7 | 14.0 | 19.7 | 890 |
| 12 x 1.5 | 0.6 | 13.7 | 19.4 | 780 |
| 12 x 2.5 | 0.7 | 16.3 | 22.4 | 1000 |
| 12 x 4.0 | 0.7 | 19.1 | 25.7 | 1410 |
| 19 x 1.5 | 0.6 | 16.2 | 22.2 | 1000 |
| 19 x 2.5 | 0.7 | 19.9 | 26.6 | 1540 |
| 19 x 4.0 | 0.7 | 22.5 | 29.3 | 1830 |
| 27 x 1.5 | 0.6 | 20.0 | 26.7 | 1500 |
| 27 x 2.5 | 0.7 | 24.0 | 30.7 | 1950 |
| 27 x 4.0 | 0.7 | 27.5 | 34.4 | 2500 |
| 37 x 1.5 | 0.6 | 22.3 | 29.0 | 1800 |
| 37 x 2.5 | 0.7 | 26.9 | 33.8 | 2350 |
| 37 x 4.0 | 0.7 | 31.0 | 39.2 | 3100 |
| 48 x 1.5 | 0.6 | 25.4 | 32.7 | 2050 |
| 48 x 2.5 | 0.7 | 31.0 | 39.3 | 3100 |
| 48 x 4.0 | 0.7 | 35.3 | 44.1 | 4100 |