Cables

6491X Cable H07V-R/H07V-U to BS6004

6491X Cable H07V-R/H07V-U to BS6004
6491X Cable H07V-R/H07V-U to BS6004

Download Cable Specification Print this page

Eland Product Group:
A2X
Application:
6491X Cable H07V-R/H07V-U to BS6004 is suitable for power and lighting circuits and building wiring. The cable is intended for use in semi-flush exposed conduits and embedded conduits as well as in closed installation ducts, and is ideal for the internal wiring of appliances and apparatus.
Standards:
BS6004
Conductor:

H07V-R: Class 2 stranded plain copper conductors to BS EN 60228:2005 (previously BS6360)
H07V-U: Class 1 solid plain copper conductor to BS EN 60228:2005 (previously BS6360)
Insulation:
PVC (Polyvinyl Chloride) Type TI1 to BS7655
Insulation Colour:
Red, Black, Blue, Yellow, Brown, White, Green/Yellow, Grey
Voltage Rating:
450/750V
Temperature Rating:
0°C to +70°C
Minimum Bending Radius:

Up to 10mm²:
3 x overall diameter

10mm² to 25mm²:
4 x overall diameter

Above 25mm²:
5 x overall diameter

RoHS Compliant

6491X Cable H07V-R/H07V-U to BS6004
No. of Cores x Nominal Cross Sectional Area # x mm² Nominal Thickness of Insulation mm Nominal Overall Diametermm Nominal Weightkg/Km
1 x 1.5 0.7 3.2 21
1 x 2.5 0.8 3.9 32
1 x 1.5 0.7 3.3 22
1 x 2.5 0.8 4.0 35
1 x 4.0 0.8 4.6 50
1 x 6.0 0.8 5.2 71
1 x 10.0 1.0 6.7 120
1 x 16.0 1.0 7.8 180
1 x 25.0 1.2 9.7 280
1 x 35.0 1.2 10.9 380
1 x 50.0 1.4 12.8 510
1 x 70.0 1.4 14.6 710
1 x 95.0 1.6 17.1 970
1 x 120.0 1.6 18.8 1200
1 x 150.0 1.8 20.9 1480
1 x 185.0 2.0 23.3 1900
1 x 240.0 2.2 26.6 2480
1 x 300.0 2.4 29.6 3100
1 x 400.0 2.6 33.2 3950
1 x 500.0 2.8 36.9 5000
1 x 630.0 2.8 41.1 6350

Download Cable Specification Print this page

sales@eland.co.uk
+44 (0)20 7241 8787

Get cable prices now!

Contact our sales team for product or pricing information on
sales@eland.co.uk
Tel +44 (0)20 7241 8787
Fax +44 (0)20 7241 8700

This cable is used within the following industries