BS5308 Instrumentation Cable Part 1 Type 2

BS5308 Instrumentation Cable Part 1 Type 2
Eland Product Group:
A3I
Application:
BS5308 cables are used to carry voice and data services, they also serve as the interconnection between electrical equipment and instruments, particularly in and around process plants, where transducer generated signals are transmitted through to panels, controllers and other devices.
Standards:
BS5308 Part 1
Conductor:
Class 1, 2 or 5 plain copper conductors to BS EN 60228:2005 (previously BS6360)
Pairing:
Two insulated conductors uniformly twisted together with a lay not exceeding 100mm
Insulation:
PE (Polyethylene) to BS6234 or XLPE (Cross Linked Polyethylene) to BS5308 for LSZH (Low Smoke Zero Halogen) cables.
Screen:

Individually Screened Pairs:
Aluminium/Polyester tape is applied to each pair, metallic side down and in continuous contact with a 0.5mm² tinned copper drain wire

Collectively Screened Cables:
Aluminium/Polyester tape is applied over the laid up pairs metallic side down and in continuous contact with a 0.5mm² tinned copper drain wire
Bedding:
PE (Polyethylene) to BS6234
Armouring:
GSWB (Galvanised Steel Wire Armour) to BS1442
Sheath:
PVC (Polyvinyl Chloride) to BS7655 or LSZH (Low Smoke Zero Halogen)
Sheath Colour:
Blue or Black
Voltage Rating:
300/500V
Temperature Rating:
65°C
Pair Identification - Individually Pair Screened:
See Pair Identification table on page 2 of the data-sheet pdf
Note:
These cables are not suitable for direct connection to the public mains supply

Specifications Data

Download detailed BS5308 Instrumentation Cable Part 1 Type 2 specifications as a PDF file (222kb)

BS5308 Instrumentation Cable Part 1 Type 2
No. of Pairs x
Nominal Cross
Sectional Area# x mm²
Nominal No. and
Nominal Diameter
of Strands#/mm
Cable Type Nominal
Diameter
Under Armourmm
Nominal
Overall Diametermm
Nominal Weightkg/Km
1 x 0.50 16/0.2 Collectively Screened 7.0 11.4 250
1 x 0.75 24/0.2 Collectively Screened 7.3 11.7 280
1 x 1.00 1/1.13 Collectively Screened 7.4 11.8 290
1 x 1.50 7/0.53 Collectively Screened 8.3 12.9 320
2 x 0.50 16/0.2 Collectively Screened 7.9 12.3 300
2 x 0.75 24/0.2 Collectively Screened 8.3 12.9 330
2 x 1.00 1/1.13 Collectively Screened 8.4 13.0 345
2 x 1.50 7/0.53 Collectively Screened 9.7 14.3 420
5 x 0.50 16/0.2 Collectively Screened 13.1 17.9 560
5 x 0.75 24/0.2 Collectively Screened 14.3 19.8 750
5 x 1.00 1/1.13 Collectively Screened 14.2 19.7 790
5 x 1.50 7/0.53 Collectively Screened 16.4 22.1 940
10 x 0.50 16/0.2 Collectively Screened 17.2 22.9 970
10 x 0.75 24/0.2 Collectively Screened 18.7 25.3 1260
10 x 1.00 1/1.13 Collectively Screened 18.4 24.3 1310
10 x 1.50 7/0.53 Collectively Screened 21.6 28.4 1500
20 x 0.50 16/0.2 Collectively Screened 22.3 29.1 1640
20 x 0.75 24/0.2 Collectively Screened 24.5 31.3 1890
20 x 1.00 1/1.13 Collectively Screened 24.4 31.2 2040
20 x 1.50 7/0.53 Collectively Screened 28.5 36.5 2500
30 x 0.50 16/0.2 Collectively Screened 26.9 33.9 1770
30 x 0.75 24/0.2 Collectively Screened 29.5 37.5 2290
30 x 1.00 1/1.13 Collectively Screened 29.0 36.2 2180
30 x 1.50 7/0.53 Collectively Screened 34.3 42.5 3170
50 x 0.50 16/0.2 Collectively Screened 33.9 42.1 2770
50 x 0.75 24/0.2 Collectively Screened 37.4 47.0 3620
50 x 1.00 1/1.13 Collectively Screened 37.3 45.7 3500
50 x 1.50 7/0.53 Collectively Screened 43.6 53.4 5020
2 x 0.50 16/0.2 Individually and
Collectively Screened
12.0 16.8 460
2 x 0.75 24/0.2 Individually and
Collectively Screened
12.8 17.6 500
2 x 1.00 1/1.13 Individually and
Collectively Screened
12.8 17.6 515
2 x 1.50 7/0.53 Individually and
Collectively Screened
14.7 20.4 730
5 x 0.50 16/0.2 Individually and
Collectively Screened
15.2 20.9 760
5 x 0.75 24/0.2 Individually and
Collectively Screened
16.3 22.0 920
5 x 1.00 1/1.13 Individually and
Collectively Screened
16.2 21.9 950
5 x 1.50 7/0.53 Individually and
Collectively Screened
18.8 25.4 1180
10 x 0.50 16/0.2 Individually and
Collectively Screened
21.1 27.9 1300
10 x 0.75 24/0.2 Individually and
Collectively Screened
22.6 29.5 1610
10 x 1.00 1/1.13 Individually and
Collectively Screened
22.6 29.4 1330
10 x 1.50 7/0.53 Individually and
Collectively Screened
26.5 33.5 1820
20 x 0.50 16/0.2 Individually and
Collectively Screened
27.3 34.3 1870
20 x 0.75 24/0.2 Individually and
Collectively Screened
29.8 37.8 2420
20 x 1.00 1/1.13 Individually and
Collectively Screened
29.8 37.8 2540
20 x 1.50 7/0.53 Individually and
Collectively Screened
34.4 42.6 3030
30 x 0.50 16/0.2 Individually and
Collectively Screened
32.3 40.5 2400
30 x 0.75 24/0.2 Individually and
Collectively Screened
35.9 43.9 3130
30 x 1.00 1/1.13 Individually and
Collectively Screened
35.4 43.8 2900
30 x 1.50 7/0.53 Individually and
Collectively Screened
41.0 50.8 4050
50 x 0.50 16/0.2 Individually and
Collectively Screened
41.7 51.5 3930
50 x 0.75 24/0.2 Individually and
Collectively Screened
45.0 55.0 4920
50 x 1.00 1/1.13 Individually and
Collectively Screened
44.9 54.9 4800
50 x 1.50 7/0.53 Individually and
Collectively Screened
52.2 62.6 5960