Tri-rated Cable
- Eland Product Group:
- A2T
- Application:
- High temperature, flame retardant cable designed for use in the switch control, relay and instrumentation panels of power switchgear and for purposes such as internal connectors in rectifier equipment, motor starters and controllers.
- Standards:
BS6231 Type CK
UL Subj.758
CSA c.22.2 No. 127 (only applicable for sizes up to 120mm²)- Conductor:
- Class 5 flexible plain copper conductors to BS EN 60228:2005 (previously BS6360)
- Insulation:
- PVC (Polyvinyl Chloride)
- Sheath Colour:
- Black, Red, Blue, Yellow, Green/Yellow, Grey,Brown, Orange, White, Violet, Green, Pink
- Voltage Rating:
BS6231: 600/1000V
UL, CSA: 600V- Temperature Rating:
BS6231: 90°C (105°C for 15,000 hours)
UL, CSA: 105°C- Minimum Bending Radius:
- 6 x overall diameter
- Note:
- Cables above 120mm² in size are referred to as Bi-rated since the CSA standard applies only to sizes up to and including 120mm²
Specifications Data
Download detailed Tri-rated Cable specifications as a PDF file (215kb)
| No. of Cores x Nominal Cross Sectional Area# x mm² |
AWG | Nominal Thickness of Insulationmm |
Nominal Overall Diametermm |
Nominal Weightkg/Km |
UL Style Number |
|---|---|---|---|---|---|
| 1 x 0.50 | 22 | 0.80 | 2.55 | 12 | 1015 |
| 1 x 0.75 | 20 | 1.14 | 2.55 | 15 | 1015 |
| 1 x 1.00 | 18 | 1.52 | 2.95 | 18 | 1015 |
| 1 x 1.50 | 16 | 0.80 | 3.20 | 23 | 1015 |
| 1 x 2.50 | 14 | 0.80 | 3.65 | 34 | 1015 |
| 1 x 4.00 | 12 | 0.80 | 4.20 | 48 | 1015 |
| 1 x 6.00 | 10 | 0.80 | 4.70 | 67 | 1015 |
| 1 x 10.00 | 8 | 1.14 | 6.50 | 119 | 1028 |
| 1 x 16.00 | 6 | 1.52 | 8.00 | 187 | 1283 |
| 1 x 25.00 | 4 | 1.52 | 9.40 | 291 | 1283 |
| 1 x 35.00 | 2 | 1.52 | 10.60 | 406 | 1283 |
| 1 x 50.00 | 1 | 2.02 | 12.90 | 580 | 1284 |
| 1 x 70.00 | 2/0 | 2.02 | 14.60 | 780 | 1284 |
| 1 x 95.00 | 3/0 | 2.02 | 16.10 | 1055 | 1284 |
| 1 x 120.00 | 4/0 | 2.02 | 17.90 | 1175 | 1284 |
| 1 x 150.00 | 250 MCM | 2.41 | 20.20 | 1425 | 1284 |
| 1 x 185.00 | 350 MCM | 2.41 | 22.85 | 1735 | 1284 |
| 1 x 240.00 | 450 MCM | 2.41 | 24.40 | 2310 | 1284 |