Armoured Cable

33kV XLPE Cable

Restriction of the use of Hazardous SubstancesBritish Standards Institute

Eland Product Group: A9M

Application: Power cables for power networks, underground, outdoors and in cable ducting.

Standards: BS6622

Conductor: Class 2 stranded plain copper conductor to BS EN 60228:2005 (previously BS6360)

Conductor screen: Semi-conducting material

Insulation: XLPE (Cross-Linked Polyethylene) Type GP8 to BS7655

Insulation Screen: Semi-conducting material

Metallic Screen: Individual and overall copper tape screen to BS6622

Filler: PETP (Polyethylene Terephthalate) fibres

Separator: Binding tape

Bedding: PVC (Polyvinyl Chloride) Type TM1 to BS7655

Armouring:
Single Core: Aluminium Wire Armoured (AWA)
Multi-core: Steel Wire Armoured (SWA)

Sheath: PVC (Polyvinyl Chloride) Type TM1 to BS7655

Colour: Red or Black

Voltage Rating: 19000/33000V

Temperature Rating: 0°C to +90°C

Minimum Bending Radius:
Single Core: 15 x overall diameter
Three Core: 12 x overall diameter
(Single Core 12 x overall diameter and 3 core 10 x overall diameter where bands are positioned adjacent to joint or terminations provided that the bending is carefully controlled by the use of a former)

For more information please consult a member of the Sales Team.

33kV XLPE Cable

Eland Part Number
Nominal Cross Sectional Area
mm²
Nominal Overall Diameter
mm
A9M33KV01070* 1 x 70 41.0
A9M33KV01095* 1 x 95 42.9
A9M33KV01120* 1 x 120 44.5
A9M33KV01150* 1 x 150 47.3
A9M33KV01185* 1 x 185 49.3
A9M33KV01240* 1 x 240 51.7
A9M33KV01300* 1 x 300 54.4
A9M33KV01400* 1 x 400 57.7
A9M33KV01500* 1 x 500 61.1
A9M33KV01630* 1 x 630 65.0
A9M33KV01800* 1 x 800 71.6
A9M33KV011000* 1 x 1000 76.5
A9M33KV03050* 3 x 50 78.2
A9M33KV03070* 3 x 70 82.1
A9M33KV03095* 3 x 95 86.1
A9M33KV03120* 3 x 120 90.0
A9M33KV03150* 3 x 150 93.2
A9M33KV03185* 3 x 185 97.5
A9M33KV03240* 3 x 240 103.3
A9M33KV03300* 3 x 300 108.8
A9M33KV03400* 3 x 400 116.1

Looking for accessories?

Try here:

Looking for cables?

Try here: