SY Control Flexible Cable to BS6500
- Eland Product Group:
- A5J
- Application:
- Used as interconnecting cable for measuring, controlling or regulation in control equipment for assembly and production lines, conveyors and for computer units. Suitable for fixed installations or for flexible use in conditions of light mechanical stress. Can be used outdoors when protected, and in dry or moist conditions indoors.
- Standards:
- Generally to BS6500, VDE0250
- Conductor:
- Class 5 flexible annealed plain copper conductors to BS EN 60228:2005 (previously BS6360), VDE0295, IEC 60228
- Insulation:
- PVC (Polyvinyl Chloride) Type YI2
- Bedding:
- PVC (Polyvinyl Chloride) Type YM2
- Braiding:
- GSWB (Galvanised Steel Wire Braid)
- Sheath:
- PVC (Polyvinyl Chloride) Type YM2
- Sheath Colour:
- Transparent
- Voltage Rating:
- 300/500V
- Temperature Rating:
Fixed: -35°C to +70°C
Flexing: -15°C to +70°C- Minimum Bending Radius:
- 10 x overall diameter
- Core Identification:
- Black with White numbers. (3 cores and above to include Green/Yellow). Coloured cores available.
- Note:
- SY Cables are not suitable for direct connection to the public mains supply.
RoHS Compliant
| No. of Cores x Nominal Cross Sectional Area # x mm² | Nominal Overall Diametermm | Nominal Weight kg/Km | FCGCXT Gland |
|---|---|---|---|
| 2 x 0.50 | 5.3 | 84 | 16/20SS |
| 2 x 0.75 | 7.5 | 73 | 20S |
| 2 x 1.00 | 7.7 | 79 | 20S |
| 2 x 1.50 | 8.5 | 96 | 20S |
| 2 x 2.50 | 9.2 | 130 | 20S |
| 3 x 0.50 | 6.3 | 85 | 16/20SS |
| 3 x 0.75 | 7.8 | 82 | 20S |
| 3 x 1.00 | 8.0 | 90 | 20S |
| 3 x 1.50 | 8.5 | 117 | 20S |
| 3 x 2.50 | 9.7 | 155 | 20S |
| 3 x 4.00 | 11.4 | 216 | 20 |
| 3 x 6.00 | 13.1 | 307 | 25 |
| 3 x 10.00 | 16.3 | 483 | 25 |
| 3 x 16.00 | 19.6 | 760 | 32 |
| 4 x 0.50 | 7.3 | 82 | 20S |
| 4 x 0.75 | 8.2 | 89 | 20S |
| 4 x 1.00 | 8.5 | 106 | 20S |
| 4 x 1.50 | 9.2 | 132 | 20S |
| 4 x 2.50 | 10.7 | 191 | 20S |
| 4 x 4.00 | 12.3 | 271 | 20 |
| 4 x 6.00 | 14.5 | 379 | 25 |
| 4 x 10.00 | 18.0 | 608 | 25 |
| 4 x 16.00 | 21.8 | 945 | 32 |
| 4 x 25.00 | 25.1 | 1349 | 32 |
| 4 x 35.00 | 29.6 | 1839 | 40 |
| 4 x 50.00 | 34.3 | 2605 | 50S |
| 4 x 70.00 | 38.5 | 3453 | 50 |
| 4 x 95.00 | 43.0 | 4544 | 50 |
| 5 x 0.50 | 8.3 | 90 | 20S |
| 5 x 0.75 | 8.8 | 101 | 20S |
| 5 x 1.00 | 9.1 | 119 | 20S |
| 5 x 1.50 | 9.7 | 147 | 20S |
| 5 x 2.50 | 11.5 | 224 | 20 |
| 5 x 4.00 | 13.8 | 330 | 25 |
| 5 x 6.00 | 16.4 | 474 | 25 |
| 5 x 10.00 | 19.5 | 734 | 32 |
| 5 x 16.00 | 23.4 | 1123 | 32 |
| 5 x 25.00 | 28.3 | 1670 | 40 |
| 5 x 35.00 | 32.0 | 2197 | 50S |
| 6 x 1.50 | 11.5 | 213 | 20 |
| 7 x 0.50 | 9.1 | 117 | 20S |
| 7 x 0.75 | 9.3 | 127 | 20S |
| 7 x 1.00 | 9.7 | 145 | 20S |
| 7 x 1.50 | 10.6 | 184 | 20S |
| 7 x 2.50 | 12.6 | 285 | 20 |
| 7 x 4.00 | 15.4 | 442 | 25 |
| 7 x 6.00 | 17.7 | 615 | 25 |
| 7 x 10.00 | 21.6 | 920 | 32 |
| 7 x 16.00 | 26.0 | 1494 | 40 |
| 8 x 1.50 | 11.7 | 207 | 20 |
| 9 x 1.50 | 13.3 | 254 | 25 |
| 12 x 0.50 | 10.6 | 153 | 20S |
| 12 x 0.75 | 11.5 | 187 | 20 |
| 12 x 1.00 | 12.1 | 226 | 20 |
| 12 x 1.50 | 13.5 | 293 | 25 |
| 12 x 2.50 | 16.6 | 460 | 25 |
| 14 x 1.50 | 14.2 | 332 | 25 |
| 18 x 0.50 | 11.6 | 255 | 20 |
| 18 x 0.75 | 13.3 | 258 | 25 |
| 18 x 1.00 | 13.8 | 311 | 25 |
| 18 x 1.50 | 16.3 | 433 | 25 |
| 18 x 2.50 | 19.3 | 654 | 32 |
| 21 x 0.50 | 13.4 | 244 | 25 |
| 21 x 0.75 | 14.3 | 368 | 25 |
| 25 x 0.75 | 16.3 | 370 | 25 |
| 25 x 1.00 | 16.9 | 438 | 25 |
| 25 x 1.50 | 19.0 | 572 | 25 |
| 25 x 2.50 | 23.2 | 891 | 32 |
| 34 x 0.75 | 18.0 | 473 | 25 |
| 34 x 1.00 | 18.5 | 561 | 25 |
| 34 x 1.50 | 21.2 | 739 | 32 |
| 42 x 1.50 | 22.8 | 906 | 32 |
| 50 x 0.75 | 20.5 | 649 | 32 |
| 50 x 1.00 | 22.4 | 794 | 32 |
| 50 x 1.50 | 28.1 | 1227 | 40 |
| 61 x 1.00 | 27.3 | 999 | 40 |
| 65 x 1.00 | 27.5 | 1091 | 40 |