Fire Performance Cable

Firecel SR 114H Standard Fire Cable PH30/PH60

Restriction of the use of Hazardous SubstancesBritish Standards Institute Loss Prevention Certification Board (LPCB)

Eland Product Group: A6F

Application: Firecel SR 114H Standard Fire Cable is primarily intended for use in fire detection and fire alarm systems, emergency lighting circuits or if cables need to properly operate when fire resistance is required.

Standards:
BS 5839-1:2002
Code of practice for fire system design, installation, commissioning and maintenance.

BS 7629-1:2008
Low emission of smoke and corrosive gases

BS EN 50200 PH30 (all sizes)
Temperature: 830 °C
Flame and shock for 30 minutes

BS EN 50200 PH60 (1.5mm² and above)
Temperature: 830 °C
Flame and shock for 60 minutes

EN 50200 Annex E (previously BS 8434-1: 2003)
Temperature: 830 °C
Flame and shock for 15 minutes.
+ flame, shock and water for 15 minutes.

BS 6387
Category C-W-Z
C - Resistance to fire at 950ºC for 3 hours
W - Resistance to fire with water at 950ºC for 3 hours
Z - Resistance to fire with mechanical shock at 950ºC for 3 hours

LPCB approved
LPCB Logo
Download Firecel SR 114H LPCB Certification as a pdf

Conductor:
Plain annealed copper to BS EN 60228:2005 (previously BS6360). Solid (Class 1) for 1 - 1.5 - 2.5mm²*. Stranded (Class 2) for 4mm².
*1.5 - 2.5mm² are available with stranded conductors (Class 2) (SR 114H-R)

Insulation:
High performance silicone rubber El2 to BS EN 50363-1

Electrostatic Screen:
Aluminium/polyester tape. 125% coverage.

Earth Conductor:
Tinned annealed copper to BS EN 60228:2005 (previously BS6360) (drain wire for multicore cables).

Sheath:
LSZH abrasion resistant, flame retardant,thermoplastic material Type LTS3 to BS 7655-6.1.

Sheath Colour: White or Red

Voltage Rating: 300/500V

Operating Temperature: -40°C to +90°C

Minimum Bending Radius: 6 x Overall Diameter

Core Identification:
2 Cores + E: Blue, Brown
3 Cores + E: Brown, Black, Grey
4 Cores + E: Blue, Brown, Black, Grey
7 Cores*: Centre: Brown
1st Layer: Brown, Black, 4 x White
12 cores*: Centre: Brown, Black, White
1st Layer: Brown, Black, 7 x White
19 cores*: Centre: Brown
1st Layer: Brown, Black, 4 x White
2nd Layer: Brown, Black, 10 x White
*Numbered Cores available on request.

Installation:
Firecel Cable is easy to handle and install without the need for specialist equipment. The cable can be attached directly to a surface using LSZH coated copper P clips, available with the cables. Plastic clips can not be used. Firecel Cable can also be installed directly into trays or conduit, or buried in plaster. Firecel Cable is suitable for use in protected outdoor environments.

For more information please consult a member of the Sales Team.

Firecel SR 114H Standard Fire Cable PH30/PH60

Eland Part Number
No. of Conductors x Nominal Cross Sectional Area
mm
Conductor Size
#/mm
Nominal Overall Diameter
mm
Net Weight
kg/km
A6F2010* 2 x 1.0 1/1.13 7.1 70
A6F3010* 3 x 1.0 1/1.13 8.0 85
A6F4010* 4 x 1.0 1/1.13 8.3 110
A6F2015* 2 x 1.5 1/1.38 8.0 95
A6F3015* 3 x 1.5 1/1.38 8.5 115
A6F4015* 4 x 1.5 1/1.38 9.4 150
A6F2025* 2 x 2.5 1/1.75 9.4 135
A6F3025* 3 x 2.5 1/1.75 10.0 170
A6F4025* 4 x 2.5 1/1.75 11.0 210
A6F2015* 2 x 1.5 7/0.53 8.4 106
A6F3015* 3 x 1.5 7/0.53 8.9 134
A6F4015* 4 x 1.5 7/0.53 9.8 166
A6F2025* 2 x 2.5 7/0.67 9.9 145
A6F3025* 3 x 2.5 7/0.67 10.3 180
A6F4025* 4 x 2.5 7/0.67 11.8 250
A6F2040* 2 x 4.0 7/0.85 11.5 210
A6F3040* 3 x 4.0 7/0.85 12.2 260
A6F4040* 4 x 4.0 7/0.85 13.5 330
A6F7010* 7 x 1.0 1/1.13 10.0 165
A6F7015* 7 x 1.5 1/1.38 11.3 225
A6F1210* 12 x 1.0 1/1.13 12.5 255
A6F1215* 12 x 1.5 1/1.38 14.5 350
A6F1910* 19 x 1.0 1/1.13 15.0 380
A6F1915* 19 x 1.5 1/1.38 17.0 520