Fire Performance Cable

Firecel SR 114E Enhanced Fire Cable PH120

Restriction of the use of Hazardous SubstancesBritish Standards Institute Loss Prevention Certification Board (LPCB)

Eland Product Group: A6F

Application: Firecel SR 114E Fire Performance Cable is intended for use in fire detection and fire alarm systems, and emergency lighting circuits. Firecel 114E Enhanced cable is recommended for situations where fire cables may need to remain operating correctly for a longer period than is expected of a standard fire cable. For example, in buildings without sprinkler systems, which have a longer evacuation process due to the size, complexity or purpose of the building, or any building that has been assessed as requiring enhanced fire protection.

Standards:
BS 5839-1:2002
Code of practice for fire system design, installation, commissioning and maintenance.

BS 7629-1:2008
Low emission of smoke and corrosive gases

BS EN 50200 PH120
Temperature: 830 °C
Flame and shock for 120 minutes

BS 8434-2:2003 +A2:2009
Temperature: 930 °C
Flame and shock for 60 minutes.
+ flame, shock and water for 60 minutes

BS 6387
Category C-W-Z
C - Resistance to fire at 950ºC for 3 hours
W - Resistance to fire with water at 950ºC for 3 hours
Z - Resistance to fire with mechanical shock at 950ºC for 3 hours

LPCB approved
LPCB Logo
Download Firecel SR 114E LPCB Certification as a pdf

Conductor:
Plain annealed copper to BS EN 60228:2005 (previously BS6360). Solid (Class 1) for 1-1.5-2.5mm²*. Stranded (Class 2) for 4mm².
*1.5 - 2.5mm² are available with stranded conductors (Class 2)

Insulation:
Mica tape plus high performance silicone rubber El2 to BS EN 50363-1.

Electrostatic Screen:
Aluminium/polyester tape. 125% coverage.

Earth Conductor:
Tinned annealed copper to BS EN 60228:2005(previously BS6360) (drain wire for multicore cables)

Sheath:
LSZH abrasion resistant, flame retardant thermoplastic material Type LTS3 to BS 7655-6.1.

Sheath Colour: Red or White

Voltage Rating: 300/500V

Operating Temperature: -40°C to +90°C

Minimum Bending Radius: 6 x Overall Diameter

Core Identification:
2 Cores + E: Blue, Brown
3 Cores + E: Brown, Black, Grey
4 Cores + E: Blue, Brown, Black, Grey
7 Cores*: Centre: Brown
1st Layer: Brown, Black, 4 x White
12 cores*: Centre: Brown, Black, White
1st Layer: Brown, Black, 7 x White
19 cores*: Centre: Brown
1st Layer: Brown, Black, 4 x White
2nd Layer: Brown, Black, 10 x White
*Numbered Cores available on request.

Installation:
Firecel Cable is easy to handle and install without the need for specialist equipment. The cable can be attached directly to a surface using LSZH coated copper P clips, available with the cables. Plastic clips can not be used. Firecel Cable can also be installed directly into trays or conduit, or buried in plaster. Firecel Cable is suitable for use in protected outdoor environments.

For more information please consult a member of the Sales Team.

Firecel SR 114E Enhanced Fire Cable PH120

Eland Part Number
No. of Conductors x Nominal Cross Sectional Area
mm
Conductor Size
#/mm
Nominal Overall Diameter
mm
Net Weight
(kg/km)
A6F2010*/ENH 2 x 1.0 1/1.13 7.9 85
A6F3010*/ENH 3 x 1.0 1/1.13 8.4 105
A6F4010*/ENH 4 x 1.0 1/1.13 9.3 125
A6F2015*/ENH 2 x 1.5 1/1.38 8.8 105
A6F3015*/ENH 3 x 1.5 1/1.38 9.3 130
A6F4015*/ENH 4 x 1.5 1/1.38 10.3 165
A6F2025*/ENH 2 x 2.5 1/1.75 10.2 150
A6F3025*/ENH 3 x 2.5 1/1.75 10.8 190
A6F4025*/ENH 4 x 2.5 1/1.75 12.0 240
A6F2015*/ENH 2 x 1.5 7/0.53 9.2 110
A6F3015*/ENH 3 x 1.5 7/0.53 9.4 135
A6F4015*/ENH 4 x 1.5 7/0.53 10.5 170
A6F2025*/ENH 2 x 2.5 7/0.67 10.3 155
A6F3025*/ENH 3 x 2.5 7/0.67 10.9 190
A6F4025*/ENH 4 x 2.5 7/0.67 12.1 250
A6F2040*/ENH 2 x 4.0 7/0.85 12.2 220
A6F3040*/ENH 3 x 4.0 7/0.85 13.0 280
A6F4040*/ENH 4 x 4.0 7/0.85 14.4 350
A6F7010*/ENH 7 x 1.0 1/1.13 10.5 175
A6F7015*/ENH 7 x 1.5 1/1.38 12.1 230
A6F1210*/ENH 12 x 1.0 1/1.13 14.5 300
A6F1215*/ENH 12 x 1.5 1/1.38 16.0 380
A6F1910*/ENH 19 x 1.0 1/1.13 17.5 470
A6F1915*/ENH 19 x 1.5 1/1.38 19.3 590