Home » Electrical Cables » High Voltage Cable » High Voltage Power Cable 2XS(F)2Y, A2XS(F)2Y

High Voltage Power Cable 2XS(F)2Y, A2XS(F)2Y

Eland Product Group: A9K

Application: The High Voltage power cables contained within this datasheet are suitable for the primary distribution of power up to a maximum network voltage of 110kV. Suitable for locations where mechanical protection is afforded by other means and where the additional protection of a moisture barrier has been determined not to be necessary, see 2XS(FL)2Y and A2XS(FL)2Y. The cables are triple extruded to the latest using proprietary materials on modern Catenary Line equipment to the latest IEC standards. Waterblocking tape options ensure that should the cable be damaged, repair lengths and associated works are kept to a minimum. The cables are provided as standard with a High Density Polyethylene chosen to give the best compromise between abrasion resistance and flexibility to ensure installation confidence. The range can be customised to meet specific project demands should the need arise.

Standards: IEC 60840, HRN HD 632

Conductor: Class 2 Copper or Aluminium Conductor, compacted or segment strand Milliken.

Conductor Screen: Extruded semi-conductive XLPE (Cross-Linked Polyethylene)

Insulation: XLPE (Cross-Linked Polyethylene)

Insulation Screen: Extruded semi-conducting XLPE (Cross-Linked Polyethylene)

Separator: Water swellable semi-conducting tape

Screen: Copper wire screen, with a counter helix of copper tape

Separator: Water swellable tape

Sheath: HDPE (High Density Polyethylene) To be specified at time of order. Other options available.

Colour: Black

Voltage Rating U0/U: 64/110kV

Highest Network Voltage Um: 123kV

Max. conductor temperature in service: (Operating temperature- continuous operation) 90

Short circuit temperature: +250ºC

Overload temperature: 130ºC (100h per year max.)

Operating Temperature: -30ºC to 90ºC

Minimum installation temperature: -20ºC

Minimum Bending Radius:
Fixed: 15 x Overall Diameter
Installation: 10 x Overall Diameter

For more information please consult a member of the Sales Team.

High Voltage Power Cable 2XS(F)2Y, A2XS(F)2Y

Eland Part Number Conductor Type No. of Cores x Nominal Cross Sectional Area and Electrical Protection# x mm2
# x mm²
Nominal Overall Diameter
mm
Nominal Weight
kg/Km
A9K2XSF150 Copper 1 x 150/95 64.5 4910
A9K2XSF185 Copper 1 x 185/95 64.1 5145
A9K2XSF240 Copper 1 x 240/95 64.4 5614
A9K2XSF300 Copper 1 x 300/95 64.7 6085
A9K2XSF400 Copper 1 x 400/95 67.4 7075
A9K2XSF500 Copper 1 x 500/95 71.3 8185
A9K2XSF630 Copper 1 x 630/95 74.8 9740
A9K2XSF800 Copper 1 x 800/95 82.6 11869
A9KA2XSF150 Aluminium 1 x 150/95 64.5 3995
A9KA2XSF185 Aluminium 1 x 185/95 64.1 4026
A9KA2XSF240 Aluminium 1 x 240/95 64.4 4156
A9KA2XSF300 Aluminium 1 x 300/95 64.7 4263
A9KA2XSF400 Aluminium 1 x 400/95 67.4 4746
A9KA2XSF500 Aluminium 1 x 500/95 71.3 5287
A9KA2XSF630 Aluminium 1 x 630/95 74.8 5908
A9KA2XSF800 Aluminium 1 x 800/95 82.6 6925
A9KA2XSF1000 Aluminium 1 x 1000/95 84.0 7409
A9KA2XSF1200* Aluminium 1 x 1200/95 90.0 8010