LSZH Flexible Cable

6381 LSZH Cable

Restriction of the use of Hazardous SubstancesBritish Standards Institute

Eland Product Group: A1F LS

Application: Suitable for D.C. power supplies on Telecom equipment and power applications where flexibility is required. The cables produce no corrosive gases when burnt which is important where electronic equipment is installed.

Conductor: Class 5 flexible annealed plain copper conductors to BS EN 60228:2005 (previously BS6360)

Insulation: XLPE (Cross-Linked Polyethylene)

Sheath: LSZH (Low Smoke Zero Halogen)

Sheath Colour (Insulation Colour): Blue (Blue), Grey (Grey), Green/Yellow (Green/Yellow), Brown (Brown), Special colours to order

Voltage Rating: 600/1000V

Temperature Rating: 90°C

Minimum Bending Radius:
Up to 50mm²: 3 x overall diameter

Above 70mm²: 4 x overall diameter

For more information please consult a member of the Sales Team.

6381 LSZH Cable

Eland Part Number
No. of Cores x Nominal Cross Sectional Area
# x mm²
Nominal Overall Diameter
mm
A1FY*/*0015LS 1 x 1.5 5.2
A1FY*/*0025LS 1 x 2.5 5.7
A1FY*/*004LS 1 x 4.0 6.6
A1FY*/*006LS 1 x 6.0 7.3
A1FY*/*010LS 1 x 10.0 8.6
A1FY*/*016LS 1 x 16.0 9.6
A1FY*/*025LS 1 x 25.0 11.5
A1FY*/*035LS 1 x 35.0 12.8
A1FY*/*050LS 1 x 50.0 14.9
A1FY*/*070LS 1 x 70.0 17.2
A1FY*/*095LS 1 x 95.0 18.6
A1FY*/*120LS 1 x 120.0 20.8
A1FY*/*150LS 1 x 150.0 23.1
A1FY*/*185LS 1 x 185.0 25.3
A1FY*/*240LS 1 x 240.0 27.8
A1FY*/*300LS 1 x 300.0 31.2
A1FY*/*400LS 1 x 400.0 35.3
A1FY*/*500LS 1 x 500.0 38.8
A1FY*/*630LS 1 x 630.0 43.8