NYCWY Power Cable

Restriction of the use of Hazardous SubstancesCenelecInternational Electrotechnical CommissionVDE (Verband der Elektrotechnik Elektronik Informationstechnik e.V.)

Eland Product Group: A9N

Application: For use where increased electrical and mechanical protection is required, preferably for underground laying, especially in subscriber networks, power stations as well as control cables for the transmission of control impulses and test data.

Standards: VDE0276 part 603, CENELEC HD603 S1, IEC 60502

Conductor:
rm conductor: Class 1 solid plain copper to BS EN 60228:2005 (previously BS6360), VDE0295, IEC 60228, CENELEC HD383
rm conductor: Class 2 stranded, round plain copper conductor, multi wire to BS EN 60228:2005 (previously BS6360), VDE0295, IEC 60228, CENELEC HD383
sm conductor: Class 2 stranded, sectorial plain copper conductor to BS EN 60228:2005 (previously BS6360), VDE0295, IEC 60228, CENELEC HD383

Insulation: PVC (Polyvinyl Chloride) DIV4 to HD 603.1

Bedding: PVC (Polyvinyl Chloride)

Concentric Conductor: Waveconal outer conductor – plain copper wires and contrahelical plain copper tape (reverse lay copper tape)

Sheath: PVC (Polyvinyl Chloride) DMV5 to HD 603.1

Sheath Colour: Black

Voltage Rating: 600/1000V

Temperature Rating:
Fixed: -30°C to +70°C
Flexing: -5°C to +50°C

Minimum Bending Radius:
Single Core: 15 x overall diameter
Multi-Core: 12 x overall diameter

Conductor Identification: Up to and including 5 cores: colour coded or number coded

For more information please consult a member of the Sales Team.

NYCWY Power Cable

Eland Part Number
No. of Cores x Nominal Cross Sectional Area
# x mm²
Stranded Conductor Type
Nominal Overall Diameter
mm
A9NYCWY02010/10 2 x 10.0 re / 10.0 19.0
A9NYCWY02016/16 2 x 16.0 re / 16.0 21.5
A9NYCWY02025/25 2 x 25.0 rm / 25.0 24.5
A9NYCWY03010/10 3 x 10.0 re / 10.0 19.5
A9NYCWY03016/16 3 x 16.0 re / 16.0 22.0
A9NYCWY03025/16 3 x 25.0 rm / 16.0 26.0
A9NYCWY03025/25 3 x 25.0 rm / 25.0 26.0
A9NYCWY03035/35 3 x 35.0 sm / 35.0 27.5
A9NYCWY03035/16 3 x 35.0 sm / 16.0 27.0
A9NYCWY03050/50 3 x 50.0 sm / 50.0 29.5
A9NYCWY03050/25 3 x 50.0 sm / 25.0 29.0
A9NYCWY03070/70 3 x 70.0 sm / 70.0 34.0
A9NYCWY03070/35 3 x 70.0 sm / 35.0 33.0
A9NYCWY03095/95 3 x 95.0 sm / 95.0 38.5
A9NYCWY03095/50 3 x 95.0 sm / 50.0 38.0
A9NYCWY03120/70 3 x 120.0 sm / 70.0 41.0
A9NYCWY03120/120 3 x 120.0 sm / 120.0 42.0
A9NYCWY03150/70 3 x 150.0 sm / 70.0 45.0
A9NYCWY03150/150 3 x 150.0 sm / 150.0 46.0
A9NYCWY03185/95 3 x 185.0 sm / 95.0 50.0
A9NYCWY03185/185 3 x 185.0 sm / 185.0 51.0
A9NYCWY03240/120 3 x 240.0 sm / 120.0 57.0
A9NYCWY04010/10 4 x 10.0 re / 10.0 20.5
A9NYCWY04016/16 4 x 16.0 re / 16.0 23.5
A9NYCWY04025/16 4 x 25.0 rm / 16.0 28.0
A9NYCWY04035/16 4 x 35.0 sm / 16.0 29.0
A9NYCWY04050/25 4 x 50.0 sm / 25.0 33.0
A9NYCWY04070/35 4 x 70.0 sm / 35.0 37.0
A9NYCWY04095/50 4 x 95.0 sm / 50.0 43.5
A9NYCWY04120/70 4 x 120.0 sm / 70.0 47.0
A9NYCWY04150/70 4 x 150.0 sm / 70.0 51.0
A9NYCWY04185/95 4 x 185.0 sm / 95.0 56.0
A9NYCWY04240/120 4 x 240.0 sm / 120.0 62.5