
Armoured Cable
Control Flexible Cable
Rubber Flexible Cable
PVC Flexible Cable
High Temperature Cable
Fixed Wiring Cable
LSZH Flexible Cable
BS5308 Instrumentation Cable
Belden Cable
Belden Alternative Cable
Fire Performance Cable
Coaxial Cable
Data Cable
Telephone Cable
Defence Standard Cable
Aluminium Conductors
Profibus and Profinet Cable
Welding Cable
Solar Cable
Signalling Cable
Power Cable
Earthing Cable
Telecom Cable
Points Heating Cable
Overhead Line Cable
Rolling Stock
Firecel SR 114E Enhanced Fire Cable PH120
Toggle
Eland Product Group: A6F
Application: Firecel SR 114E Fire Performance Cable is intended for use in fire detection and fire alarm systems, and emergency lighting circuits. Firecel 114E Enhanced cable is recommended for situations where fire cables may need to remain operating correctly for a longer period than is expected of a standard fire cable. For example, in buildings without sprinkler systems, which have a longer evacuation process due to the size, complexity or purpose of the building, or any building that has been assessed as requiring enhanced fire protection.
Standards:
BS 5839-1:2002
Code of practice for fire system design,
installation, commissioning and maintenance.
BS 7629-1:2008
Low emission of smoke and corrosive gases
BS EN 50200 PH120
Temperature: 830 °C
Flame and shock for 120 minutes
BS 8434-2:2003 +A2:2009
Temperature: 930 °C
Flame and shock for 60 minutes.
+ flame, shock and water for 60 minutes
BS 6387
Category C-W-Z
C - Resistance to fire at 950ºC for 3 hours
W - Resistance to fire with water at 950ºC for 3 hours
Z - Resistance to fire with mechanical shock at 950ºC for 3 hours
LPCB approved
Download Firecel SR 114E LPCB Certification as a pdf
Firecel SR 114H Standard Fire Cable PH30/PH60
Toggle
Eland Product Group: A6F
Application: Firecel SR 114H Standard Fire Cable is primarily intended for use in fire detection and fire alarm systems, emergency lighting circuits or if cables need to properly operate when fire resistance is required.
Standards:
BS 5839-1:2002
Code of practice for fire system design, installation, commissioning and maintenance.
BS 7629-1:2008
Low emission of smoke and corrosive gases
BS EN 50200 PH30 (all sizes)
Temperature: 830 °C
Flame and shock for 30 minutes
BS EN 50200 PH60 (1.5mm² and above)
Temperature: 830 °C
Flame and shock for 60 minutes
EN 50200 Annex E (previously BS 8434-1: 2003)
Temperature: 830 °C
Flame and shock for 15 minutes.
+ flame, shock and water for 15 minutes.
BS 6387
Category C-W-Z
C - Resistance to fire at 950ºC for 3 hours
W - Resistance to fire with water at 950ºC for 3 hours
Z - Resistance to fire with mechanical shock at 950ºC for 3 hours
LPCB approved
Download Firecel SR 114H LPCB Certification as a pdf
