6491X Cable H07V-R/H07V-U

- Eland Product Group:
- A2X
- Application:
- Suitable for use in conduit and for fixed, protected installation.
- Standards:
- BS6004
- Conductor:
- Stranded class 2: plain annealed copper conductors to BS 6360
- Insulation:
- PVC (Type TI1 to BS7655)
- Colour:
- Red, Black, Blue, Yellow, Brown, White, Green/Yellow, Grey
- Voltage Rating:
- 450/750V
- Temperature Rating:
- 0 to +70°C
- Minimum Bending Radius:
Up to 10mm²:
3 x overall diameter
10mm² to 25mm²:
4 x overall diameter
Above 25mm²:
5 x overall diameter
Specifications Data
Download detailed 6491X Cable H07V-R/H07V-U specifications as a PDF file (256kb)
| No. of Cores x Nominal Cross Sectional Area # x mm² | Nominal Thickness of Insulation mm | Nominal Overall Diametermm | Nominal Weightkg/Km |
|---|---|---|---|
| 1 x 1.5 | 0.7 | 3.2 | 21 |
| 1 x 2.5 | 0.8 | 3.9 | 32 |
| 1 x 1.5 | 0.7 | 3.3 | 22 |
| 1 x 2.5 | 0.8 | 4.0 | 35 |
| 1 x 4.0 | 0.8 | 4.6 | 50 |
| 1 x 6.0 | 0.8 | 5.2 | 71 |
| 1 x 10.0 | 1.0 | 6.7 | 120 |
| 1 x 16.0 | 1.0 | 7.8 | 180 |
| 1 x 25.0 | 1.2 | 9.7 | 280 |
| 1 x 35.0 | 1.2 | 10.9 | 380 |
| 1 x 50.0 | 1.4 | 12.8 | 510 |
| 1 x 70.0 | 1.4 | 14.6 | 710 |
| 1 x 95.0 | 1.6 | 17.1 | 970 |
| 1 x 120.0 | 1.6 | 18.8 | 1200 |
| 1 x 150.0 | 1.8 | 20.9 | 1480 |
| 1 x 185.0 | 2.0 | 23.3 | 1900 |
| 1 x 240.0 | 2.2 | 26.6 | 2480 |
| 1 x 300.0 | 2.4 | 29.6 | 3100 |
| 1 x 400.0 | 2.6 | 33.2 | 3950 |
| 1 x 500.0 | 2.8 | 36.9 | 5000 |
| 1 x 630.0 | 2.8 | 41.1 | 6350 |