Home » Rail Cables » Power Cables » 11kV XLPE MDPE Cable

11kV XLPE MDPE Cable

Eland Product Group: A9M

Application: Power cables for power networks, underground and in cable ducting.

Standards: BS6622

Network Rail Acceptance Certificate Number: PA05/04787

Conductor: Class 2 stranded plain copper conductor to BS EN 60228:2005 (previously BS6360)

Conductor Screen: Semi-conducting material

Insulation: XLPE (Cross-Linked Polyethylene)Type GP8 to BS7655

Insulation Screen: Semi-conducting material

Metallic Screen: Individual and overall copper tape screen to BS6622

Filler: PETP (Polyethylene Terephthalate) fibres

Separator: Binding tape

Bedding: PVC (Polyvinyl Chloride) Type TM1 to BS7655

Separator: Water Blocking Tape

Armouring: SWA (Steel Wire Armoured)

Sheath: MDPE (Medium Density Polyethylene) type TS2

Sheath Colour: Red or Black

Voltage Rating: 6350/11000V

Temperature Rating: 0 to +90ÂșC

Minimum Bending Radius: Three Cores: 12 x overall diameter

Note: (3 cores 10 x overall diameter where bends are positioned adjacent to joint or terminations provided that the bending is carefully controlled by the use of a former)

For more information please consult a member of the Sales Team.

11kV XLPE MDPE Cable

Eland Part Number No. of Cores x Nominal Cross Sectional Area
# x mm²
PAD's Number Nominal Diameter Overall
mm
Nominal Weight
kg/Km
A9M11KV03185-BK 3 x 185 006/120036 74.1 11000
A9M11KV03185-RD 3 x 185 006/120037 74.1 11000