SWA Cable - BS6724 Steel Wire Armoured LSZH
- Eland Product Group:
- A9S
- Application:
- SWA Cable - power and auxiliary control cables for use in power networks, underground, outdoor and indoor applications and for use in cable ducting. For installation where fire, smoke emission and toxic fumes create a potential threat to life and equipment.
- Standards:
- BS6724
- Conductor:
- Class 2 stranded plain annealed copper conductor to BS EN 60228:2005 (previously BS6360)
- Insulation:
- XLPE (Cross-Linked Polyethylene)
- Bedding:
- LSZH (Low Smoke Zero Halogen)
- Armouring:
Single Core: AWA (Aluminium Wire Armour)
Multi Core: SWA (Steel Wire Armour)- Sheath:
- LSZH (Low Smoke Zero Halogen)
- Sheath Colour:
- Black
- Voltage Rating:
- 600/1000V
- Temperature Rating:
- 0°C to +90°C
- Minimum Bending Radius:
1.5mm² - 16mm²:
6 x overall diameter
25mm² and above:
8 x overall diameter- Core Identification:
1 Core: Brown
2 Cores: Brown, Blue
3 Cores: Brown, Black, Grey
4 Cores: Blue, Brown, Black, Grey
5 Cores: Green/Yellow, Blue, Brown, Black, Grey
Alternative core identification: White Cores with Black numbers
RoHS Compliant
| No. of Cores x Cross Sectional Area# x mm² | Nominal Thickness of Insulationmm | Nominal Diameter Under Armourmm | Nominal Overall Diametermm | Nominal Weightkg/Km |
|---|---|---|---|---|
| 1 x 50 | 1.0 | 12.7 | 17.5 | 800 |
| 1 x 70 | 1.1 | 14.7 | 20.2 | 960 |
| 1 x 95 | 1.1 | 16.6 | 22.3 | 1240 |
| 1 x 120 | 1.2 | 18.5 | 24.2 | 1510 |
| 1 x 150 | 1.4 | 20.8 | 27.4 | 1900 |
| 1 x 185 | 1.6 | 23.2 | 30.0 | 2320 |
| 1 x 240 | 1.7 | 26.0 | 32.8 | 2930 |
| 1 x 300 | 1.8 | 28.6 | 35.6 | 3580 |
| 1 x 400 | 2.0 | 32.4 | 40.4 | 4600 |
| 1 x 500 | 2.2 | 36.0 | 44.2 | 5770 |
| 1 x 630 | 2.4 | 40.0 | 48.8 | 7250 |
| 1 x 800 | 2.6 | 45.6 | 55.4 | 9381 |
| 1 x 1000 | 2.8 | 50.6 | 60.6 | 11540 |
| 2 x 1.5 | 0.6 | 7.3 | 12.1 | 302 |
| 2 x 2.5 | 0.7 | 8.5 | 13.6 | 346 |
| 2 x 4.0 | 0.7 | 9.4 | 14.7 | 410 |
| 2 x 6.0 | 0.7 | 10.5 | 15.9 | 499 |
| 2 x 10.0 | 0.7 | 12.3 | 18.0 | 648 |
| 2 x 16.0 | 0.7 | 14.3 | 20.4 | 978 |
| 2 x 25.0 | 0.9 | 14.7 | 20.4 | 1290 |
| 2 x 35.0 | 0.9 | 16.8 | 23.3 | 1500 |
| 2 x 50.0 | 1.0 | 19.0 | 25.8 | 1890 |
| 2 x 70.0 | 1.1 | 22.0 | 29.0 | 2450 |
| 2 x 95.0 | 1.1 | 25.1 | 33.1 | 3300 |
| 2 x 120.0 | 1.2 | 27.9 | 36.1 | 4020 |
| 2 x 150.0 | 1.4 | 30.9 | 39.3 | 4750 |
| 2 x 185.0 | 1.6 | 34.9 | 44.7 | 6180 |
| 2 x 240.0 | 1.7 | 39.0 | 49.0 | 7570 |
| 3 x 1.5 | 0.6 | 7.8 | 12.6 | 330 |
| 3 x 2.5 | 0.7 | 9.2 | 14.1 | 390 |
| 3 x 4.0 | 0.7 | 10.0 | 15.3 | 464 |
| 3 x 6.0 | 0.7 | 11.2 | 16.6 | 568 |
| 3 x 10.0 | 0.7 | 13.1 | 19.5 | 866 |
| 3 x 16.0 | 0.7 | 15.3 | 21.6 | 1152 |
| 3 x 25.0 | 0.9 | 18.9 | 25.5 | 1800 |
| 3 x 35.0 | 0.9 | 21.3 | 28.0 | 2230 |
| 3 x 50.0 | 1.0 | 21.7 | 28.5 | 2490 |
| 3 x 70.0 | 1.1 | 25.2 | 32.2 | 3290 |
| 3 x 95.0 | 1.1 | 28.8 | 37.0 | 4440 |
| 3 x 120.0 | 1.2 | 32.0 | 40.4 | 5470 |
| 3 x 150.0 | 1.4 | 35.9 | 45.5 | 6930 |
| 3 x 185.0 | 1.6 | 40.0 | 49.8 | 8350 |
| 3 x 240.0 | 1.7 | 44.9 | 55.1 | 10400 |
| 3 x 300.0 | 1.8 | 49.8 | 60.2 | 12600 |
| 3 x 400.0 | 2.0 | 55.8 | 66.6 | 14600 |
| 4 x 1.5 | 0.6 | 8.5 | 13.5 | 365 |
| 4 x 2.5 | 0.7 | 9.9 | 15.0 | 438 |
| 4 x 4.0 | 0.7 | 11.0 | 16.4 | 532 |
| 4 x 6.0 | 0.7 | 12.3 | 18.7 | 764 |
| 4 x 10.0 | 0.7 | 14.5 | 21.1 | 1013 |
| 4 x 16.0 | 0.7 | 17.0 | 22.9 | 1360 |
| 4 x 25.0 | 0.9 | 21.0 | 27.6 | 2160 |
| 4 x 35.0 | 0.9 | 23.6 | 30.4 | 2690 |
| 4 x 50.0 | 1.0 | 25.0 | 32.0 | 3130 |
| 4 x 70.0 | 1.1 | 29.5 | 37.7 | 4500 |
| 4 x 95.0 | 1.1 | 33.3 | 41.7 | 5600 |
| 4 x 120.0 | 1.2 | 37.5 | 47.1 | 7400 |
| 4 x 150.0 | 1.4 | 41.6 | 51.4 | 8780 |
| 4 x 185.0 | 1.6 | 46.4 | 56.6 | 10630 |
| 4 x 240.0 | 1.7 | 52.6 | 63.0 | 13390 |
| 4 x 300.0 | 1.8 | 58.0 | 68.8 | 16290 |
| 4 x 400.0 | 2.0 | 65.4 | 78.1 | 19800 |
| 5 x 1.5 | 0.6 | 9.7 | 14.3 | 410 |
| 5 x 2.5 | 0.7 | 11.7 | 16.3 | 470 |
| 5 x 4.0 | 0.7 | 13.0 | 17.8 | 710 |
| 5 x 6.0 | 0.7 | 14.5 | 20.0 | 876 |
| 5 x 10.0 | 0.7 | 17.2 | 22.9 | 1165 |
| 5 x 16.0 | 0.7 | 20.0 | 26.6 | 1742 |
| 5 x 25.0 | 0.9 | 24.7 | 31.5 | 2323 |
| 5 x 35.0 | 0.9 | 27.8 | 34.8 | 2932 |
| 5 x 50.0 | 1.0 | 32.4 | 40.4 | 4192 |
| 5 x 70.0 | 1.1 | 37.9 | 46.3 | 5336 |
| 7 x 1.5 | 0.6 | 10.2 | 15.2 | 470 |
| 7 x 2.5 | 0.7 | 12.3 | 17.1 | 600 |
| 7 x 4.0 | 0.7 | 14.0 | 19.7 | 890 |
| 12 x 1.5 | 0.6 | 13.7 | 19.4 | 780 |
| 12 x 2.5 | 0.7 | 16.3 | 22.4 | 1000 |
| 12 x 4.0 | 0.7 | 19.1 | 25.7 | 1410 |
| 19 x 1.5 | 0.6 | 16.2 | 22.2 | 1000 |
| 19 x 2.5 | 0.7 | 19.9 | 26.6 | 1540 |
| 19 x 4.0 | 0.7 | 22.5 | 29.3 | 1830 |
| 27 x 1.5 | 0.6 | 20.0 | 26.7 | 1500 |
| 27 x 2.5 | 0.7 | 24.0 | 30.7 | 1950 |
| 27 x 4.0 | 0.7 | 27.5 | 34.4 | 2500 |
| 37 x 1.5 | 0.6 | 22.3 | 29.0 | 1800 |
| 37 x 2.5 | 0.7 | 26.9 | 33.8 | 2350 |
| 37 x 4.0 | 0.7 | 31.0 | 39.2 | 3100 |
| 48 x 1.5 | 0.6 | 25.4 | 32.7 | 2050 |
| 48 x 2.5 | 0.7 | 31.0 | 39.3 | 3100 |
| 48 x 4.0 | 0.7 | 35.3 | 44.1 | 4100 |