Trackfeeder Cable
Download Cable Specification Print this page
- Eland Product Group:
- A3T
- Application:
- Provides the 650/750 volt DC supply from Traction Substations and Track Paralleling Huts to conductor rails, negative cable connections and where appropriate, bonding
- Standards:
- NR/PS/ELP/21101 (formerly RT/E/S/21101)
- Conductor:
- Class 2 stranded aluminium or tinned copper to BS EN 60228:2005 (previously BS6360)
- Separator:
- PETP (Polyethylene Terephthalate)
- Sheath:
- CSP (Chlorosulphonated Polyethylene) Type RS4 to BS6899
- Sheath Colour:
- Black
- Voltage Rating:
- 650/750V
- Temperature Rating:
- -25°C to +85°C
- Minimum Bending Radius:
Aluminium conductor:
10 x overall diameter
Copper conductor:
8 x overall diameter
Trackfeeder Cable
| Rail Catalogue Number |
Nominal Cross Sectional Areamm² |
Conductor Material |
No. and Nominal Diameter of Strands#/mm |
Nominal Overall Diametermm |
Assigned Continuous Current RatingAmps |
| 006/116610 |
1000 |
Aluminium |
127/3.20 |
53.0 |
1500 |
| 006/116612 |
630 |
Copper |
127/2.52 |
44.2 |
1500 |
| 006/132840 |
500 |
Aluminium |
61/3.20 |
40.2 |
800 |
| 006/132991 |
800 |
Aluminium |
127/2.85 |
48.5 |
1200 |
| 006/132992 |
500 |
Copper |
91/2.65 |
40.6 |
1200 |
| 006/132990 |
240 |
Aluminium |
61/2.25 |
28.3 |
550 |
| 006/132340 |
161 |
Copper |
91/1.53 |
24.8 |
550 |
| 006/116601 |
150 |
Aluminium |
37/2.25 |
19.4 |
430 |
Download Cable Specification Print this page