Armoured Cable
Control Flexible Cable
Rubber Flexible Cable
PVC Flexible Cable
High Temperature Cable
Fixed Wiring Cable
LSZH Flexible Cable
BS5308 Instrumentation Cable
Belden Cable
Belden Alternative Cable
Fire Performance Cable
Coaxial Cable
Data Cable
Telephone Cable
Defence Standard Cable
Aluminium Conductors
Profibus and Profinet Cable
Welding Cable
Solar Cable
Signalling Cable
Power Cable
Earthing Cable
Telecom Cable
Points Heating Cable
Overhead Line Cable
Rolling Stock
Power Cables
MV Power Cable
Eland Product Group: A9M
Application: Cable used to distribute three phase a.c. electrical power supplies at nominal system voltages of 33kV to traction substations on D.C. electrified lines.
Standards: NR/PS/ELP/00008 (formerly RT/E/PS/00008) BS6622, BS6234, BS7454, IEC 60502-2, IEC 60840
Conductor:
185mm²: Class 1 circular solid aluminium to BS EN 60228:2005 (previously BS6360)
300mm²: Class 2 compact circular stranded plain copper to BS EN 60228:2005
(previously BS6360)
Conductor Screen: Extruded semi-conducting XLPE (Cross-Linked Polyethylene), solidly bonded
Insulation: XLPE (Cross-Linked Polyethylene)
Insulation Screen : Extruded semi-conducting XLPE (Cross-Linked Polyethylene), solidly bonded, strippable
Bedding Tape: Water swellable semi-conducting tape
Screen: Copper wire screen, helically wound with equalising copper tape
Separator: Water swellable tape
Sheath: Graphite coated MDPE (Medium Density Polyethylene) type TS2
Sheath Colour: Black
Voltage Rating: 19000/33000V
Temperature Rating: +90˚C
Minimum Bending Radius: 15 x overall diameter (12 x overall diameter adjacent to joints or terminations provided that bending is carefully controlled by use of former)
Spike Test: Eland Cables performed a Spike Test on samples of 33kV cable to prove that the screen of the cable can withstand a full specified fault current for a period of no less than 3 seconds. It simulates the accidental “spiking” of a live cable installation and ensures that the circuit protection will operate and the circuit fails to safety.

Watch Video
For more information please consult a member of the Sales Team.
MV Power Cable
| Eland Part Number |
Rail Catalogue Number |
No. of Cores x Nominal Conductor Area # x mm² |
Nominal Overall Diameter mm |
|---|---|---|---|
| A9M1185ALSOLID | 006/122514 | 1 x 185 | 45 |
| A9M1300CUST | 006/122511 | 1 x 300 | 50 |
Looking for accessories?
Try here:
Looking for cables?
Try here: