Flame Retardant Cables and Fire Integrity in reference to Cables - what is the difference?

Flame Retardant refers to a cable’s ability to restrict the propagation of flames in the event of a fire. This is especially important where cables pass from one area to another within a building in order to slow down any spreading of the fire. This is tested by setting fire to a cable in a verticle chamber and measuring the extent to which the flame moves up the cable. There are different categories of loading (A, B or C) depending on the intended use of the cable. The purchaser can select the category appropriate to the required application.
Fire Integrity refers to the amount of times a cable can be exposed to a flame and continue to function. Typical applications of these types of cables are for use in fire alarms, and circuit systems.

Featured Downloads


Featured Products

Firecel SR 114E Enhanced Fire Cable PH120Firecel SR 114E Enhanced Fire Cable PH120 Toggle

Eland Product Group: A6F

Application: Firecel SR 114E Fire Performance Cable is intended for use in fire detection and fire alarm systems, and emergency lighting circuits. Firecel 114E Enhanced cable is recommended for situations where fire cables may need to remain operating correctly for a longer period than is expected of a standard fire cable. For example, in buildings without sprinkler systems, which have a longer evacuation process due to the size, complexity or purpose of the building, or any building that has been assessed as requiring enhanced fire protection.

Standards:
BS 5839-1:2002
Code of practice for fire system design, installation, commissioning and maintenance.

BS 7629-1:2008
Low emission of smoke and corrosive gases

BS EN 50200 PH120
Temperature: 830 °C
Flame and shock for 120 minutes

BS 8434-2:2003 +A2:2009
Temperature: 930 °C
Flame and shock for 60 minutes.
+ flame, shock and water for 60 minutes

BS 6387
Category C-W-Z
C - Resistance to fire at 950ºC for 3 hours
W - Resistance to fire with water at 950ºC for 3 hours
Z - Resistance to fire with mechanical shock at 950ºC for 3 hours

LPCB approved
LPCB Logo
Download Firecel SR 114E LPCB Certification as a pdf

VIEW PRODUCT DETAILS

Firecel SR 114H Standard Fire Cable PH30/PH60Firecel SR 114H Standard Fire Cable PH30/PH60 Toggle

Eland Product Group: A6F

Application: Firecel SR 114H Standard Fire Cable is primarily intended for use in fire detection and fire alarm systems, emergency lighting circuits or if cables need to properly operate when fire resistance is required.

Standards:
BS 5839-1:2002
Code of practice for fire system design, installation, commissioning and maintenance.

BS 7629-1:2008
Low emission of smoke and corrosive gases

BS EN 50200 PH30 (all sizes)
Temperature: 830 °C
Flame and shock for 30 minutes

BS EN 50200 PH60 (1.5mm² and above)
Temperature: 830 °C
Flame and shock for 60 minutes

EN 50200 Annex E (previously BS 8434-1: 2003)
Temperature: 830 °C
Flame and shock for 15 minutes.
+ flame, shock and water for 15 minutes.

BS 6387
Category C-W-Z
C - Resistance to fire at 950ºC for 3 hours
W - Resistance to fire with water at 950ºC for 3 hours
Z - Resistance to fire with mechanical shock at 950ºC for 3 hours

LPCB approved
LPCB Logo
Download Firecel SR 114H LPCB Certification as a pdf

VIEW PRODUCT DETAILS

 
 