Fixed Wiring Cables

6491B Conduit Wiring Cable H07Z-R to BS7211

6491B Conduit Wiring Cable H07Z-R to BS7211
6491B Conduit Wiring Cable H07Z-R to BS7211
Eland Product Group:
A3Z
Application:
Suitable for use in conduit and for fixed, protected installation. In particular for installation where fire, smoke emission and toxic fumes create a potential threat.
Standards:
BS7211
Conductor:
Class 2 stranded plain copper conductors to BS EN 60228:2005 (previously BS6360)
Insulation:
LSZH (Low Smoke Zero Halogen)
Insulation Colour:
Black, Blue, Green/Yellow, Red, Yellow, White, Violet, Brown,
Grey, Orange, Pink
Voltage Rating:
450/750V
Temperature Rating:
0°C to +90°C
Minimum Bending Radius:

Up to 10mm²:
3 x overall diameter

10mm² to 25mm²:
4 x overall diameter

Above 25mm²:
5 x overall diameter

RoHS Compliant

Specifications Data

Download detailed 6491B Conduit Wiring Cable H07Z-R to BS7211 specifications as a PDF file (362kb)

6491B Conduit Wiring Cable H07Z-R to BS7211
No. of Cores x Nominal Cross Sectional Area # x mm² Nominal Thickness of Insulation mm Nominal Overall Diametermm Nominal Weightkg/Km
1 x 1.5 0.7 3.4 22
1 x 2.5 0.8 4.2 35
1 x 4.0 0.8 4.8 50
1 x 6.0 0.8 5.4 72
1 x 10.0 1.0 6.8 121
1 x 16.0 1.0 8.0 182
1 x 25.0 1.2 9.8 285
1 x 35.0 1.2 11.0 390
1 x 95.0 1.6 17.0 980
1 x 120.0 1.6 19.0 1220
1 x 150.0 1.8 21.0 1500
1 x 185.0 2.2 23.5 1910
1 x 240.0 2.2 26.5 2490
1 x 300.0 2.4 29.5 3100
1 x 400.0 2.6 33.5 3950
1 x 500.0 2.8 37.0 5000
1 x 630.0 2.8 41.0 6350