Trackfeeder Cable
- Eland Product Group:
- A3T
- Application:
- Provides the 650/750 volt DC supply from Traction Substations and Track Paralleling Huts to conductor rails, negative cable connections and where appropriate, bonding
- Standards:
- NR/PS/ELP/21101 (formerly RT/E/S/21101)
- Conductor:
- Class 2 stranded aluminium or tinned copper to BS EN 60228:2005 (previously BS6360)
- Separator:
- PETP (Polyethylene Terephthalate)
- Sheath:
- CSP (Chlorosulphonated Polyethylene) Type RS4 to BS6899
- Sheath Colour:
- Black
- Voltage Rating:
- 650/750V
- Temperature Rating:
- -25°C to +85°C
- Minimum Bending Radius:
Aluminium conductor:
10 x overall diameter
Copper conductor:
8 x overall diameter
Specifications Data
Download detailed Trackfeeder Cable specifications as a PDF file (282kb)
| Rail Catalogue Number | Nominal Cross Sectional Areamm² | Conductor Material | No. and Nominal Diameter of Strands#/mm | Nominal Overall Diametermm | Assigned Continuous Current RatingAmps |
|---|---|---|---|---|---|
| 006/116610 | 1000 | Aluminium | 127/3.20 | 53.0 | 1500 |
| 006/116612 | 630 | Copper | 127/2.52 | 44.2 | 1500 |
| 006/132840 | 500 | Aluminium | 61/3.20 | 40.2 | 800 |
| 006/132991 | 800 | Aluminium | 127/2.85 | 48.5 | 1200 |
| 006/132992 | 500 | Copper | 91/2.65 | 40.6 | 1200 |
| 006/132990 | 240 | Aluminium | 61/2.25 | 28.3 | 550 |
| 006/132340 | 161 | Copper | 91/1.53 | 24.8 | 550 |
| 006/116601 | 150 | Aluminium | 37/2.25 | 19.4 | 430 |